T775A/B/M SERIES 2000 CONTROLLER
PROGRAM
RELAY 1
SETBACK
Fig. 32. Program - Setback.
Fig. 33. Program - Exit.
62-0254–03
MENU
PROGRAM
RELAY 1
SETBACK
60
o
F
ENTER
SETBACK
SETPOINT
FOR RELAY 1
M24498
MENU
PROGRAM
MOD 1
MOD 2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
M24499
1.2.5. SETBACK
The Setback temperature option displays if scheduling is
enabled (see Fig. 55 on page 24) or the DI Option is set to
Setback. (see Fig. 57 on page 25).
This is the desired setpoint temperature that you want to
use during setback mode for this output. For example, if
your setpoint is 70°F and you want the temperature to
drop 10°F during setback mode, enter 60°F as the set-
point for this output.
1. From the menu, use the
light SETBACK.
2. Use the
and
desired setpoint temperature.
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
3. Press the
button to accept the value and display
the menu.
1.2.6. Program Next Output
For the next output (Mod or Relay), select the desired
output from the Program menu (see Fig. 26 on page 14).
Go to "1.2.1. SETPOINT" on page 14 to program the next
output.
When you finish programming the outputs, continue with
"1.2.7. Exiting Program Mode" on page 16.
1.2.7. Exiting Program Mode
Press the HOME button to leave programming mode and
return to the home screen.
This completes the programming procedure.