6.2 Modbus address table

(1) DO status (Function Code:1,5,15)
Address(Dec)
Address(Hex)
00129
00130
(2) DI status (Function Code:2)
Address
Data Address
00000
0x00
00001
0x01
00002
0x02
00003
0x03
00004
0x04
00005
0x05
(3) AI status(Function Code:4)
Address
Data Address
30027
0x1B
30028
0x1C
Note:
1.
AI value(Hex) conversion formulas: AI = (AI Hex * 20) / FFF
2.
AI value(engineering)
Example:
(1) If read AI value(Hex) is "FF"
AI = (FF * 20) /FFF = (255*20)/4095 = 1.25 mA
(2) If read AI value(engineering) is "1250"
AI = 1250/1000 = 1.25mA
If function code = 1
Read DO0
0x81
If function code = 5,15
Set DO0, 1:High, 0:Low
If function code = 1
Read DO1
0x82
If function code = 5,15
Set DO1, 1:High, 0:Low
Read AI value (engineering)
conversion formulas: AI = AI(engineering)/1000