Industrial Computer Products Data Acquisition System
RMV-511
Intelligent Multiport Serial to GPRS Gateway with I/O
User manual V1.0
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RMV-511 and is the answer not in the manual?

Questions and answers

Summary of Contents for ICP DAS USA RMV-511

  • Page 1 Industrial Computer Products Data Acquisition System RMV-511 Intelligent Multiport Serial to GPRS Gateway with I/O User manual V1.0...
  • Page 2 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the data of delivery to the original purchaser. Warning ICP DAS assumes no liability for damages consequent to the use of this product.
  • Page 3: Table Of Contents

    4.7.6 Inquiring Firmware Version ........................28 How to use the RMV-511 Utility through the Virtual com to access remote the parameters of the RMV-511 ..29 The necessary software installed ........................29 Setting the VxServer and VxComm Driver ....................30 Modbus RTU Protocol ............................
  • Page 4: Introduction

    I/O monitor. The user-friendly Axiom Driver/Utility and VxServer allow users to easily turn the built-in COM ports of the RMV-511 into standard COM ports on a PC. By virtue of its protocol independence, a small-core OS and high flexibility, the RMV-511 is able to meet the demands of every network-enabled application.
  • Page 5: Applications

    1.2 Applications  PLC remote maintenance  Remote serial devices monitor...
  • Page 6: Hardware

    2. Hardware 2.1 Specifications System 32 bit CPU SRAM 64 Kbytes Flash Memory 512 Kbytes Gives time(sec, min, hour) & data, leap year compensation WDT(watchdog) GSM/GPRS Module Frequency Band Quad-band: 850/900/1800/1900 MHz Class 4 (2 W @ 850/900 MHz) Compliant with GSM Phase 2/2+ Class 1 (1 W @ 1800/1900 MHz) Coding Schemes CS 1, CS 2, CS 3, CS 4...
  • Page 7 Analog Input Channels Resolution 12 bits Input Range/Type 0~20 mA Power Protection Reverse polarity protection Frame Ground Protection ESD, Surge, EFT, Hi-Pot Required Supply Voltage +10 VDC ~ +30 VDC Mechanical Casing Plastic Flammability UL 94V-0 materials Dimensions (W x L x H) 91 mm x 132 mm x 52 mm Installation DIN-Rail...
  • Page 8: Appearance And Pin Assignments

    2.2 Appearance and Pin Assignments The following figure shows the appearance of RMV-511. DI/DO COM Port & Power Input Terminal Terminal Assignment Assignment Ground for COM Utility Port RxD1 RS-232 TxD1 COM1 RS-485 RST+ Reset DI COM DI COM RST-...
  • Page 9: Dimensions

    2.3 Dimensions...
  • Page 10: Di/Do Internal Structure And Wire Connection

    2.4 DI/DO internal Structure and Wire Connection (1) DO Internal Structure (2) DI Internal Structure...
  • Page 11: Led Indicators

    (2) GSM (Green): The modem LED can indicate the status of GSM module. GSM module normal GSM module failed Blinking (3 sec) Blinking (not 3 sec) (3) STA (Orange): The system LED indicated whether the RMV-511 is normal of failed. Successful First Use No connected to VxServer...
  • Page 12: Installing Rmv-511

    2.6 Installing RMV-511 If users want to start RMV-511 normally, it needs to follow these steps to install the RMV-511 below: Install the GSM antenna Plug in the normal SIM card (Before apply the SIM card, confirm it is OK by mobile phone.)
  • Page 13: Installing The Rmv-511 Utility

    3.1 Installing .NET Framework It needs the runtime environment with .NET Framework 2.0 or above to execute the RMV-511 Utility in the PC. If there has .NET Framework 2.0 or above in the PC, the section 3.1 can be omitted.
  • Page 14 Press "Next" to the next step. 2. Select the "I accept the terms of the License Agreement" and "Install" to the next step.
  • Page 15 3. The installation process would be going 4. After finishing the installation, press "Finish" to exit the program.
  • Page 16: Installing The Rmv-511 Utility

    3.2 Installing the RMV-511 Utility Plug in the shipment CD into the PC, Execute\RMV-511\Software\RMV-511_Utility_Setup_Vx.xx.exe The installation figure is as follows: 1. Press "Next" to start the installation procedure. 2. Select the installation path. The default path is "C:\ICPDAS\RMV-511_Utility". Press “Next” to the next step.
  • Page 17 3. Select the "Start Menu Folder", Press "Next" to the next step. 4. Select additional tasks. Press "Next" to the next step...
  • Page 18 5. Click "Install" to start to install the RMV-511 Utility 6. Click "Finish" to finish installing RMV-511 Utility...
  • Page 19: The Rmv-511 Utility Operation Description

    These tools include all the function operation of the RMV-511 Utility. The description is as the following: 1. Project: The parameters of the RMV-511 can be saved as the project file. The operation functions include "New", "Open", "Save", "Save as…", and etc...
  • Page 20 (4) Description: A particular or minute account (5) Status Bar: This bar can show the operation procedure of the RMV-511 Utility. From left to right, they are: 1. The used com port number 2. Communication configuration of the COM Port 3.
  • Page 21: File Menu

    For connecting to the RMV-511, you can follow the steps below. (1) Select the COM port of the host PC and connect to the Utility port of RMV-511. (2) Press "Connect" to connect to the RMV-511. If the connection is failed, check...
  • Page 22: Parameters

    The parameters would be shown in the right of the windows if click the tree field in the left side of the RMV-511 Utility. Press the parameters’ “Value” filed can change these parameters as the following figure. There are 12 items in the system field below.
  • Page 23: Download/Upload Parameters

    (1) Download parameters As the configuration is finishing, the function can download the parameters to the RMV-511 by clicking “Download” as the following figure. (2) Upload Parameters "Uploading" button can upload the parameters from the RMV-511 as the following figure.
  • Page 24: I/O Monitor

    4.6 I/O Monitor (1) Press "I/O monitor" can show the I/O status. (2) This function is used to control DO0 and DO1 channels and show the status of DI channels and AI value. It will automation get the IO status per 5 sec. Text field: A.
  • Page 25: System

    Click "System->Signal Quality" can show the signal quality windows to know the GSM signal strength. Field Description: The strength is divided into 5 sections shown in percentage. Operation: Read:Read the GSM signal strength from the RMV-511. 4.7.2 Reboot the RMV-511 Clicking "System->Reboot RMV-511" button can reset the RMV-511 as follows.
  • Page 26: Inputting The Pin/Puk

    4.7.3 Inputting the PIN/PUK When the RMV-511 starts and the STA LED is blanking per 50 ms, it is needed to input the PIN or PUK code in the RMV-511. In this condition, click “System->Input PIN/PUK” button to set the PIN/PUK code.
  • Page 27: Recover To The Factory Settings

    4.7.4 Recover to the Factory Settings It can recover the RMV-511 to the default settings by clicking "System->Recover Default Settings". 4.7.5 Inquiring System status Press "SystemSystem status" in tool menu, and the window would show the RMV-511 working status Field instruction: ...
  • Page 28: Inquiring Firmware Version

    4.7.6 Inquiring Firmware Version Press "System->Firmware Version" in tool menu, and the window would show the versions of the RMV-511 Utility and firmware.
  • Page 29: How To Use The Rmv-511 Utility Through The Virtual Com To Access Remote The Parameters Of The Rmv-511

    5. How to use the RMV-511 Utility through the Virtual com to access remote the parameters of the RMV-511 5.1 The necessary software installed Installing .NET Compact Framework Installing VxServer Installing VxComm Drivr Installing RMV-511 Utility  Download Microsoft .Net Framework Version 2.0: http://www.microsoft.com/downloads/details.aspx?FamilyID=0856eacb-4362-4b0...
  • Page 30: Setting The Vxserver And Vxcomm Driver

    5.2 Setting the VxServer and VxComm Driver (1) Verify that the device has been connected up (2) Execute VxComm Utility, then click "Search Servers"...
  • Page 31 (3) Select your device, then click "Add Server(s)" (4) IP Range=> check "Maps virtual COM ports to "Port I/O" on servers".
  • Page 32 (5) Advanced Options, please follow the below parameter settings Parameters Fixed value Keep Alive Time Connection Broken Connect Timeout Command Port 10000 Virtual I/O Port 9999...
  • Page 33 Port I/O Port 1 Port I/O :The port I/O can configure the system parameter via RMV-511 utility, it can also get the I/O status and control the DO. I/O control methods please refer the chapter 6. Port 1:The Port 1 mapping to the COM1 of RMV-511...
  • Page 34 (8) According the Port I / O of VxComm Utility to select the com port of RMV-511 Utility, then click "RMV-511 Utility => Connect" (9) The remaining steps, please refer to Chapter 4...
  • Page 35: Modbus Rtu Protocol

    2400bps to 115200 bps. The number of data bits is fixed to 8, the parity and stop bits are fixed as no parity and 1 stop bit. The Modbus function codes supported in the RMV-511 are 1,2,4,5 and 15. The Modbus address distribution is as the following table, its Net ID is 1.
  • Page 36 04 ~ 05 AI count 2 Byte  Response Net ID 1 Byte Function code 1 Byte Byte count of response (B=2*AI count) 1 Byte 03 ~ (B+2) AI value 3-(B+2) Byte Set Digital Output (Function code:5)  Request Net ID 1 Byte Function code 1 Byte...
  • Page 37: Modbus Address Table

    6.2 Modbus address table (1) DO status (Function Code:1,5,15) Address(Dec) Address(Hex) Description Attribute If function code = 1 Read DO0 00129 0x81 If function code = 5,15 Set DO0, 1:High, 0:Low If function code = 1 Read DO1 00130 0x82 If function code = 5,15 Set DO1, 1:High, 0:Low (2) DI status (Function Code:2)