Modbus Address Table - ICP DAS USA RMV-511 User Manual

Table of Contents

Advertisement

6.2 Modbus address table

(1) DO status (Function Code:1,5,15)
Address(Dec)
00129
00130
(2) DI status (Function Code:2)
Address
Data Address
00000
00001
00002
00003
00004
00005
(3) AI status(Function Code:4)
Address
Data Address
30027
30028
Note:
1.
AI value(Hex) conversion formulas: AI = (AI Hex * 20) / FFF
2.
AI value(engineering)
Example:
(1) If read AI value(Hex) is "FF"
AI = (FF * 20) /FFF = (255*20)/4095 = 1.25 mA
(2) If read AI value(engineering) is "1250"
AI = 1250/1000 = 1.25mA
Address(Hex)
0x81
0x82
0x00
0x01
0x02
0x03
0x04
0x05
0x1B
0x1C
conversion formulas: AI = AI(engineering)/1000
Description
If function code = 1
Read DO0
If function code = 5,15
Set DO0, 1:High, 0:Low
If function code = 1
Read DO1
If function code = 5,15
Set DO1, 1:High, 0:Low
Description
Read DI0
Read DI1
Read DI2
Read DI3
Read DI4
Read DI5
Description
Read AI value (hex)
Read AI value (engineering)
37
Attribute
R/W
R/W
Attribute
R
R
R
R
R
R
Attribute
R
R