Chimney Active (Service Mode)
WARNING
The Chimney Active (service mode) button puts the boiler into service mode which allows
adjustment of high fire/low fire and O2 settings. To enter Chimney Active (service mode):
1
From the controller Home screen,
press and hold the Chimney Active
button for approximately 7 seconds.
Home
screen
2
The following screen appears
indicating that Chimney Active
(service mode) is active.
Rinnai M-Series Condensing Boiler Combi Manual
This section should be performed by a licensed professional. Consumers
should never attempt any action that they are not qualified to perform.
3
Chimney Active (service mode) defaults
to 100%.
Use the selector wheel to adjust
between 0% to 100% and then press
OK.
•
0% (boiler will run on low fire/low
load)
•
100% (boiler will run on maximum
fire/full load)
4
To exit Chimney Active (service mode),
press the Back button until the Home
screen appears on the display.
87