This boiler is configured for Natural Gas
only. To convert to Propane Gas, follow the
instructions in this section.
WARNING
The conversion kit shall be installed by
a qualified service agency in
accordance with the manufacturer's
instructions and all applicable codes
and requirements of the authority
having jurisdiction. The information in
these instructions must be followed
exactly to minimize the risk of fire or
explosion or to prevent property
damage, personal injury or death. The
qualified service agency is responsible
for the proper installation of this kit.
The installation is not proper and
complete until the operation of the
converted appliance is checked as
specified in the manufacturer's
instructions supplied with the kit.
Failure to correctly assemble the
components according to these
instructions may result in a gas leak or
explosion.
For installations in Canada, the conversion shall
be carried out in accordance with the
requirements of the provincial authorities
having jurisdiction and in accordance with the
requirements of the CGA-B149.1, Natural Gas
and Propane Installation Code.
The appliance must be installed in accordance
with:
Local codes or, in the absence of local
codes, the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1,
Natural Gas and Propane Installation Code.
The Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280
and/or CAN/CSA Z240 MH Series, Mobile
Homes, Series M86 / Manufactured Home
Construction and Safety Standard, Title 24
CFR.
Rinnai M-Series Condensing Boiler Combi Manual
CAUTION
The gas supply shall be shut off prior to
disconnecting the electrical power, before
proceeding with the conversion.
CAUTION
Do not touch any other areas on the PC
board other than the described buttons
while power is supplied to the appliance.
Parts of the PC board are supplied with 120
volts AC.
CAUTION
Do not touch the areas at or near the heat
exchanger or hot water lines. These areas
become very hot and could cause burns.
IMPORTANT
Before you get started, confirm that
the inlet gas pressure is between the
minimum and maximum pressures
allowed for this boiler.
If subsequent conversions are made,
then a new conversion label must be
placed on the boiler to accurately
reflect the gas type.
Conversion Kit (supplied with boiler)
Adjustable wrench
Combustion analyzer
109