Rinnai M060C Installation And Operation Manual page 82

Wall-mounted, gas-fired combi condensing boiler
Table of Contents

Advertisement

Below are some typical target temperatures for various heat emitters.
Type of Heat Emitter
Hydronic Air Handler
Unit Heater
Base Board convectors
Cast Iron / Panel Radiator
Undermount Radiant
Poured concrete radiant
*NOTE: These are basic guidelines. Please check with manufacturer of emitter or consult your
heating design engineer.
Below are parameter locations and explanations of outdoor reset parameters that will need to be
adjusted upon installation.
Parameter
Description
Address
4.2.0
Curve Presets
4.2.2
Slope
4.2.5
Maximum
temperature
4.2.6
Minimum
temperature
82
Typical Minimum Supply
Temperature
120 - 140°F
130 - 140°F
100 - 140°F
90 - 120°F
100 -120°F
80 - 90°F
Key Outdoor Reset Parameters
1=High temperature, (all apps except in-floor (slab) radiant
applications)
2= Low temperature, (in-floor) slab radiant apps
High value = steep slope
Low value = gradual slope
Raises / lowers maximum target supply temperature
Raises / lowers minimum target supply temperature and
outdoor reset curve.
Rinnai M-Series Condensing Boiler Combi Manual
Typical Maximum Supply
Temperature
140 - 180°F
160 - 180°F
140 - 190°F
140 - 180°F
120 - 150°F
110 - 130°F
Value