Heating Parameters
PARA
Default
4.2.0
1
4.2.1
3
LT=0.8
4.2.2
HT=2.0
4.2.3
0
LT=122°F
4.2.5
HT=185°F
4.2.6
68°F
Service Parameters
PARA
Unit
8.0.1
Hours
8.0.3
Hours
8.0.4
Hours
8.0.5
Cycles
8.0.6
Cycles
8.0.7
Cycles
76
Range
OK=YES
ESC=NO
0=NO
1=NC
0=OFF
System (plant) frost protection, pump operation based
1=ON
Range
0=Low Temp
1= High Temp
Thermoregulation: outdoor temperature reset
0=OFF
Also available from AUTO function in main menu (CH)
3=ON
LT=0.2-1.0
Slope of outdoor reset curve (see separate slides),
HT=1.0=3.5
Depends on
curve settings
LT=68-122°F
HT=68-185°F
LT=68-122°F
HT=68-185°F
Total hours boiler on power (electricity)
Rinnai M-Series Condensing Boiler Combi Manual
Description
Resets all parameters to factory defaults
(green button)
External Safety contact (LWCO, etc)
(NOTE: DO NOT USE OPTION 2)
on outdoor temp sensor value
Description
Outdoor reset curve presets
or 2.2.4
DO NOT USE 1,2, or 4
depends on 4.2.0 setting
Heating curve offset (parallel shift)
Maximum supply temp (°F)
Minimum supply temp (°F)
Description
Total pump hours
Total fan hours
Total fan cycles
Total CH flame ignitions
Total DHW flame ignitions