Connect the Condensate Drain Kit
Tools/Materials Required
Multi-purpose grease or lubricant
Verify Contents
Item
Item
#
a
Elbow with flexible pipe
b
T-piece, elbow and flexible pipe
assembly
c
Flexible drain pipe
d
Condensate drain inner tube
e
Condensate drain outer tube
f
Condensate collector cover
Instructions
Reference Figure 1 for the following
instructions.
1. Press and turn the assembly (3), with the
elbow first, in the corresponding holes in the
bottom plate of the boiler.
2. Press the black flexible pipe (1) from inside
the boiler in the rubber T-piece (3).
3. Press the black rubber elbow with flexible
drain pipe (1) on the condensate tray (2).
4. Lead the long black flexible pipe (4) through
the free hole of the boiler frame and press it
in the T-piece (3).
5. Lead the other end of the flexible pipe
outside the boiler to the drain.
6. Fill the condensate drain outer tube (5) with
150 ml (about 5 oz.) of water.
7. Apply multi-purpose grease or lubricant to
the top of the o-ring on the condensate drain
inner tube (6).
8. Insert the condensate drain inner tube (6)
through the hole in the bottom plate of the
boiler into the condensate tray (2) of the
heat exchanger; you will hear a click when it
is fully seated. Next, insert the condensate
drain outer tube through the hole. Secure
the condensate drain out tube with the
securing clip (7) by turning it clockwise.
9. Press the sealing ring (8) around the outer
condensate tube and press/turn it in the
bottom plate of the boiler.