Quick Start Guide
1200-RD00-00-0-x Programmable PID Controller
GETTING STARTED
• Unpack Contents
• Verify model numberand application
• Power Controller
• Program for yourapplication
Note
Change all menu parameters by
using the front panel buttons
1
What's Included
• 48x96 DIN 1200-RD00-00-0-x
Gefran Controller
• Mounting Bracket
• Panel Sealing Gasket
• Screw Terminal Cover
• Multi-Language Manual
2
Program Your Gefran Controller
• Press and hold
until PAS appears — ENTER 99
F
• Press
F
once, Pro appears — ENTER 128
• Press
F
once, PAS appears — ENTER 99
• Press and hold
until Hrd appears
F
• Press
twice, Ctr appears — ENTER14
F
AL.n
• Press
once,
appears — ENTER 0
F
CFG
• Press and hold
F
until
appears
C.Me
• Press and hold
F
until
appears
— ENTER 0 cooling with Air
— ENTER 1 cooling with Oil
— ENTER 0 cooling with Water
until1 nP appears
• Press and hold
F
• Press
F
twice, tYP appears — ENTER the Input Sensor number
• Press
repeatedly until Lo.S* appears — ENTER the minimum Input Scale limit
F
once, H i.S* appears — ENTER the maximum Input Scale limit
• Press
F
• Press
repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
F
once, H i.L* appears — ENTER the maximum Alarm Scale limit
• Press
F
Out
• Press and hold
F
until
appears
• Press
F
once, rl.1 appears — ENTER1
• Press and hold
until you return to the main process display. This is the display after PAS
F
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr,
Err if no input is connected.
• Use the and buttons to adjust the control setpoint (SV) from the main display.
• Press the
button to switch between automatic and manual control modes from the
main display. LED 1(
) will light while in manual mode.
L1
* Parameter may be left at default value for input types 0...37
Input Sensor
Sensor Type
Sensor Type
0
TC J °C
30 PT100 °C
1
TC J °F
31 PT100 °F
2
TC K °C
32 JPT100 °C
3
TC K °F
33 JPT100 °F
4
TC R °C
34 PTC °C
5
TC R °F
35 PTC °F
6
TC S °C
36 NTC °C
7
TC S °F
37 NTC °F
8
TC T °C
44 4...20 mA
9
TC T °F
46 0...10 V
Via Sebina, 74 - 25050 PROVAGLIO D'ISEO (BS) ITALY
Heat - Cool
3
Connect Your Controller
Additional wiring
8
configurations
are available
in the User's
7
Manual and
General Setup
Guide
6
5
2
11
10
1
POWER
If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
With the machine at ambient temperature and
the control setpoint (SV) set...
• Press and hold
until CFG appears
F
• Press
once, S.Tu appears — ENTER 2
F
• Press
once
F
• Cycle power to the controller
• LED 3 (
) will flash during the tuning process
L3
Self-Tune will automatically save new PID
values once complete
This Quick Start Guide provides basic information on
setting up the Gefran 1200 controller for the application
referenced above. Additional software and hardware
configuration information can be found in the User's Manual
included with this controller or online at www.gefran.com
GEFRAN SpA
COOLING
-
+
HEATER
POWER CONTROL
-
+
THERMOCOUPLE