Command/Response Reference
Results Storage Area Response Codes
Note

7-3-17 TCP CLOSE REQUEST

Command Block
Response Block
Results Storage Format
Response code
2211
High traffic at Unit; cannot execute service.
2240
Socket service mode is incorrect; cannot execute service.
(With unit version 1.5 or later, the high-speed socket service
option was enabled and a socket service was used with a
CMND(490) instruction.)
Response code
0000
Normal
0020
Connection to the remote socket was broken during transmis-
sion (EPIPE).
003E
Internal buffer cannot be reserved due to high receive load
(ENOBUFS).
0042 (see note)
An error occurred (EMSGSIZE).
0044 (see note)
Received ICMP data (ENOPROTOOPT).
0045 (see note)
A communication error occurred with the remote node
(ECONNABORTED).
004B (see note)
A communication error occurred with the remote node
(ECONNRESET).
004E (see note)
A parameter error occurred at the remote IP address
(ENETUNREACH).
004F (see note)
Received ICMP data (EHOSTDOWN).
0051 (see note)
A parameter error occurred at the remote IP address
(EHOSTUNREACH).
0053 (see note)
A communication error occurred with the remote node
(ETIMEDOUT).
0081
The specified socket was closed during transmission.
These errors occur only in large multilayered networks.
Requests processing to close a TCP socket. Other processing being carried
out is forcibly ended and a code is recorded in the results storage area.
27 14
Command
Results storage area
code
TCP socket number
Socket option
27 14
Command
Response
code
code
Response code
Section 7-3