6.3.8.1.
Disable Zoning
This option allows the installer to enable or disable zoning. After the selection is
made, touch SAVE.
Disable Zoning: Yes or No
S
Default = No
d
6.3.8.2.
Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or
deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to
change the zone. After the selection is made, touch SAVE.
Temperature Offset: Adjustable between - - 5 to 5_F (- - 3 to 3_C)
S
Default = 0_F
d
6.3.8.3.
Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to select the
maximum allowable noise/airflow relationship into each zone based on air noise
and comfort requirements. LOW means 100% of maximum assessed airflow;
MED- - LOW means 138% of maximum assessed airflow; MEDIUM means 176%
of maximum assessed airflow; MED- - HIGH means 214% of maximum assessed
55