(- - 9 to 13_C) or None
Default = None
d
Defrost with Furnace, Electric Heat or Hydronic: Yes or No
S
Default = Yes
d
For Geothermal units, lockout for auxiliary heat (furnace or electric resis-
d
tance) is not enabled.
NOTE: When simultaneous heating and cooling demand feature is ON, the system
will try to respect the settings for heat source but may override the settings if the
preferred heat source is unable to deliver heat.

6.3.6. Stages / Latch for 18VS

For 18VS heat pumps, the cooling and heating stage/latch can be changed. Select
cooling or heating next to stages/latch. The maximum stage and the minimum stage
can be selected. The minimum selected stage can be locked- - in or set based upon
the outside temperature.
6.3.7.
Geothermal HP
First touch SETUP, then touch Geo HP to set up the parameters for the Geo HP
unit.
51
A14228A