Ac Output Cables Connection - ABB PVS-175-TL-SX2 Product Manual

175 kw
Table of Contents

Advertisement

A
C output cables connection
Before carrying out any operation, check that any external AC switch downstream to the
inverter (grid side) are in OFF position and check for voltage absence on the AC conductors!
Single-core
AC panel version
11
T
S
R
12
Multi-core
AC panel version (optional)
11
R
T
S
12
Routing of the AC cables inside the inverter must be carried out from the
right side of the inverter.
Depending of the version of the AC panel installed on the inverter it will
be necessary to route the AC output and ground cables into different
ways:
- Single-core configuration (default): 3xM40 cable glands
"R", "S", "T" phases and a M32 cable gland
In this configuration the AC output and ground cables must be inserted
into the proper cable glands, trying to follow a logical order based on the
position of the internal connections:
R = Phase R (indicated with a label near the AC connection busbar
S = Phase S (indicated with a label near the AC connection busbar
T = Phase T (indicated with a label near the AC connection busbar
The ground connection can be made using the Protective earth point (int.)
, Protective earth point (ext.)
26
in force in certain countries of installation).
= Ground (indicated with the protective earth symbol
protection earth connection point (int.)
point (ext.)
).
10
- Multi-core configuration (optional):
"R", "S", "T" phases and a M32 cable gland
This version of the AC panel can be ordered separately. Refer to "Kit of
recommended spare parts" chapter for further information.
Follow the procedure below to route all the cables:
• Open the wiring box front cover
• Remove the AC protective shield
- 72 -
for the grounding cable.
12
or both (this is required by regulations
10
or protection earth connection
26
one M63 cable gland
for the grounding cable.
12
.
07
by removing the M5 screw.
27
27
5 - Installation
for the
11
)
22
)
22
)
22
near the
for the
11

Advertisement