Additional Features - Ei Electronics Ei603MRF Instructions Manual

Battery powered smoke & heat alarms
Table of Contents

Advertisement

Caution: Do not House Code another group (e.g. adjacent apartment) until the
current House Code has been completed.
Factory Reset
Sometimes in order to resolve an RF communication issue it may be necessary to
reset (factory reset) and House Code the system again. To do so, press and hold the
House Code button until you see a flashing blue light on the Alarm cover (approx. 7
seconds), release immediately. Repeat this procedure on all other Alarms.

Additional Features

The Ei600MRF RadioLINK + Module provides additional features not available
with Ei Electronics RadioLINK products. The following features will only work with
RadioLINK + devices.
1. Remote House Coding (required if you want to add an Alarm to an installed system)
2. Monitoring
3. Data Extraction
*Note these functions will not be available unless you have completed House Code Entry
1. Remote House Coding
If it is necessary to extend an RF system or you find that you want to add an
extra Alarm to a system you can now do so quite simply via the 'Remote House
Coding' feature. Firstly remove any Alarm in an RF system from its mounting plate
and press the House Code button on this device. Hold the button until you see all
colours flashing (red, blue, green) and then release. This Alarm will now send an
RF message to all the previously installed (compatible) devices to re-enter House
www.acornfiresecurity.com