Daikin Altherma EPGA011-016DV Installer's Reference Manual page 94

Low temperature split
Hide thumbs Also See for Altherma EPGA011-016DV:
Table of Contents

Advertisement

2/10
Field settings table
Breadcrumb Field code
Setting name
Room
└─ Antifrost
1.4.1
[2-06]
Activation
1.4.2
[2-05]
Room setpoint
└─ Setpoint range
1.5.1
[3-07]
Heating minimum
1.5.2
[3-06]
Heating maximum
1.5.3
[3-09]
Cooling minimum
1.5.4
[3-08]
Cooling maximum
Room
1.6
[2-09]
Room sensor offset
1.7
[2-0A]
Room sensor offset
Main zone
2.4
Setpoint mode
└─ Heating WD curve
2.5
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
2.5
[1-01]
High ambient temp. for LWT main zone heating WD curve.
2.5
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
2.5
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
└─ Cooling WD curve
2.6
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
2.6
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
2.6
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
2.6
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Main zone
2.7
[2-0C]
Emitter type
└─ Setpoint range
2.8.1
[9-01]
Heating minimum
2.8.2
[9-00]
Heating maximum
2.8.3
[9-03]
Cooling minimum
2.8.4
[9-02]
Cooling maximum
Main zone
2.9
[C-07]
Control
2.A
[C-05]
Thermostat type
└─ Delta T
2.B.1
[1-0B]
Delta T heating
2.B.2
[1-0D]
Delta T cooling
└─ Modulation
2.C.1
[8-05]
Modulation
2.C.2
[8-06]
Max modulation
└─ Shut off valve
2.D.1
[F-0B]
During thermo
2.D.2
[F-0C]
During cooling
Additional zone
3.4
Setpoint mode
└─ Heating WD curve
3.5
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
3.5
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
3.5
[0-02]
High ambient temp. for LWT add zone heating WD curve.
3.5
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
└─ Cooling WD curve
3.6
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
3.6
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
3.6
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
3.6
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
4P556072-1 - 2018.12
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
0: Disabled
1: Enabled
4~16°C, step: 1°C
8°C
12~18°C, step: 0,5°C
12°C
18~30°C, step: 0,5°C
30°C
15~25°C, step: 0,5°C
15°C
25~35°C, step: 0,5°C
35°C
-5~5°C, step: 0,5°C
0°C
-5~5°C, step: 0,5°C
0°C
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
-40~5°C, step: 1°C
-10°C
10~25°C, step: 1°C
15°C
[9-01]~[9-00], step: 1°C
35°C
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
10~25°C, step: 1°C
20°C
25~43°C, step: 1°C
35°C
[9-03]~[9-02]°C, step: 1°C
22°C
[9-03]~[9-02]°C, step: 1°C
18°C
0: Underfloor heating
1: Fancoil unit
2: Radiator
15~37°C, step: 1°C
25°C
[2-0C]=2:
37~60, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
5~18°C, step: 1°C
8°C
18~22°C, step: 1°C
22°C
0: LWT control
1: Ext RT control
2: RT control
0: -
1: 1 contact
2: 2 contacts
3~10°C, step: 1°C
5°C
3~10°C, step: 1°C
5°C
0: No
1: Yes
0~10°C, step: 1°C
5°C
0: No
1: Yes
0: No
1: Yes
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
[9-05]~[9-06]°C, step: 1°C
50°C
10~25°C, step: 1°C
15°C
-40~5°C, step: 1°C
-10°C
[9-07]~[9-08]°C, step: 1°C
8°C
[9-07]~[9-08]°C, step: 1°C
12°C
25~43°C, step: 1°C
35°C
10~25°C, step: 1°C
20°C
Installer setting at variance with
default value
Date
Value
(*1) *6V_(*2) *9W_
(*3) *AB*_(*4) EAV*_
(*5) *X*_(*6) *H*_
(*7) EAV*18*_(*8) EAV*23*

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents