Daikin Altherma EPGA011-016DV Installer's Reference Manual page 56

Low temperature split
Hide thumbs Also See for Altherma EPGA011-016DV:
Table of Contents

Advertisement

8 Configuration
INFORMATION
When powerful operation is active, the risk of space
heating/cooling and capacity shortage comfort problems is
significant. In case of frequent domestic hot water
operation, frequent and long space heating/cooling
interruptions will happen.
Comfort setpoint
Only applicable when domestic hot water preparation is Schedule
only or Schedule + reheat. When programming the schedule, you
can make use of the comfort setpoint as a preset value. When you
later want to change the storage setpoint, you only have to do it in
one place.
The tank will heat up until the storage comfort temperature has
been reached. It is the higher desired temperature when a storage
comfort action is scheduled.
Additionally, a storage stop can be programmed. This feature puts a
stop to tank heating even if the setpoint has NOT been reached.
Only program a storage stop when tank heating is absolutely
undesirable.
#
Code
[5.2]
[6-0A]
Comfort setpoint
▪ 30°C~[6‑0E]°C
Eco setpoint
The storage economic temperature denotes the lower desired
tank temperature. It is the desired temperature when a storage
economic action is scheduled (preferably during day).
#
Code
[5.3]
[6-0B]
Eco setpoint
▪ 30°C~min(50,[6‑0E])°C
Reheat setpoint
Desired reheat tank temperature, used:
▪ in Schedule + reheat mode, during reheat mode: the guaranteed
minimum tank temperature is set by the Reheat setpoint minus the
reheat hysteresis. If the tank temperature drops below this value,
the tank is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature rises above this value,
domestic hot water preparation and space heating/cooling are
executed sequentially.
#
Code
[5.4]
[6-0C]
Reheat setpoint
▪ 30°C~min(50,[6‑0E])°C
Schedule
You can set the tank temperature schedule using the schedule
screen. For more information about this screen, see
screen: Example" on
page 44.
Heat up mode
The domestic hot water can be prepared in 3 different ways. They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.
Installer reference guide
56
Description
Description
Description
"8.3.8 Schedule
#
Code
[5.6]
[6-0D]
Heat up mode
▪ 0: Reheat only: Only reheat operation
is allowed.
▪ 1: Schedule + reheat: The domestic
hot water tank is heated according to a
schedule and between the scheduled
heat up cycles, reheat operation is
allowed.
▪ 2: Schedule only: The domestic hot
water tank can ONLY be heated
according to a schedule.
See the operation manual for more details.
INFORMATION
Risk of space heating capacity shortage for domestic hot
water tank without internal booster heater: In case of
frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when
selecting the following:
Tank > Heat up mode > Reheat only.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.
#
Code
[5.7.1]
[2‑01]
Activation
▪ 0: No
▪ 1: Yes
[5.7.2]
[2‑00]
Operation day
▪ 0: Every day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[5.7.3]
[2‑02]
Start time
[5.7.4]
[2‑03]
Tank setpoint
55°C~75°C
[5.7.5]
[2‑04]
Duration
5~60 minutes
EPGA11~16DAV3 + EABH/X16DA6V+9W
Description
Description
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10