Figure 18. Example of Wiring a Low-Side Switch to the Fault Input

Enable Output

The Enable output signal is an optically isolated digital output used to enable or disable the drive for the
axis. The Enable signal for the axis is deactivated when any of the following signals are asserted:
Host Bus Interlock (global)
Inhibit All (user-supplied and global)
User-supplied external Fault input (per axis)
Controller Axis Inhibit Out (per axis)
Controller Shutdown (if enabled on the controller)
If the Enable output signal is deactivated for any reason, the DISABLED LED illuminates. If the Fault
input signal is also active, both the FAULT and the DISABLED LEDs for the axis illuminate. Refer to
Figure 14 for the locations of these LEDs.
Refer to the
Global Stop
interlock is a safety feature that is not user-configurable. It monitors the +5 V pin from the motion
controller to verify that the motion controller is powered on and properly connected to the UMI-7774/72.
NI UMI-7774/72 User Guide and Specifications