Download Print this page

Unitronics Jazz JZ20-J-UN20 Installation Manual page 5

Micro-plc+hmi
Hide thumbs Also See for Jazz JZ20-J-UN20:

Advertisement

Thermocouple
 Thermocouple 0: use T- Input as
negative input and T+ as positive.
RTD
Unitronics
 PT100 (Sensor 0): use both inputs related to CM signal
Type
Temp. Range
mV
-5 to 56mV
200 to 1820˚C
B
(300 to 3276˚F)
-200 to 750˚C
E
(-328 to 1382˚F)
-200 to 760˚C
J
(-328 to 1400˚F)
-200 to 1250˚C
K
(-328 to 2282˚F)
-200 to 1300˚C
N
(-328 to 3214˚F)
0 to 1768˚C
R
(32 to 3214˚F)
0 to 1768˚C
S
(32 to 3214˚F
-200 to 400˚C
T
(-328 to 752˚F)
05/16
Wire Color
ANSI
BS1843
(USA)
(UK)
+Grey
+None
-Red
-Blue
+Violet
+Brown
-Red
-Blue
+White
+Yellow
-Red
-Blue
+Yellow
+Brown
-Red
-Blue
+Orange
+Orange
-Red
-Blue
+Black
+White
-Red
-Blue
+Black
+White
-Red
-Blue
+Blue
+White
-Red
-Blue
5

Advertisement

loading

This manual is also suitable for:

Jazz jz20-un20