Table 10: Troubleshooting
Problem
Fault and Bypass indicators and all LED
segments of the Battery Level indicator are
illuminated
Fault and Bypass indicators and Diagnostic A
indicator are illuminated
Fault and Bypass indicators and Diagnostic B
indicator are illuminated
Fault and Bypass indicators and Diagnostic C
indicator are illuminated
Fault indicator and Diagnostic C indicator are
illuminated
Fault and Bypass indicators and Diagnostic E
indicator are illuminated
Fault indicator and Diagnostic A and C indica-
tors are illuminated
Fault and Bypass indicators and Diagnostic C
and E indicator are illuminated
Fault indicator and Diagnostic A and B indica-
tors are illuminated
AC Input indicator is flashing
Battery indicator is flashing
Bypass indicator is flashing
Cause
UPS is overloaded or the load is faulty
UPS shutdown due to temperature conditions
Load is on bypass power
UPS internal DC bus overvoltage
UPS DC/DC fault
UPS PFC (Power Factor Correction Circuit) fault
UPS inverter fault
UPS failed the battery test
UPS shut down by a command from the
communication port(s)
UPS failure (includes dual-fan failure, single-fan
failure under certain conditions, and battery
charger failure)
UPS detected a line-to-neutral reversal or a loss
of proper grounding for the UPS. A continuous
alarm will sound; the UPS cannot start up in
standby status.
This is active only when power is first applied
to the input. Once the UPS is running, the
AC input indicator will flash, unless the input
wiring is correctly changed.
Battery source is not available
The bypass is disabled because the voltage or
frequency is outside the acceptable limits
S4K2U-5C SEriES USEr mAnUAL | 41
Solution
Check the Load Level indicator and remove
non-essential loads. recalculate the load and
reduce the number of loads connected to the
UPS. Check the load for faults.
Ensure the UPS is not overloaded, ventila-
tion holes are not blocked, or room ambient
temperature is not excessive. Wait 30 minutes
to allow the UPS to cool, then restart the UPS.
if the UPS cannot restart, contact your local
dealer, SolaHD representative or SolaHD Tech-
nical Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
replace the batteries. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for replacement battery packs.
UPS has received a signal or command from
the attached computer. if this was inadvertent,
ensure the communication cable used is correct
for your system. For assistance, contact SolaHD
Technical Support.
Ensure fan is not blocked up. if the fault is not
resolved, contact SolaHD Technical Support for
assistance.
Contact a qualified electrician to verify site
wiring.
Check battery connections, completely power
down and restart the UPS.
NOTE: if the battery circuit opens while the UPS
is running, it will be detected when the next
battery test is performed.
The AC input powers the PFC input and serves
as the bypass source. if the AC is present but
the voltage or frequency exceeds the accept-
able range for safe operation with a load, the
bypass will be disabled and this indicator will
flash, indicating that the bypass is unavailable.