SDU AC-A Series
A272-290
Rev. 5 07/2018
Uninterruptible Power Supply

Advertisement

Table of Contents
loading

Summary of Contents for Emerson SolaHD SDU 500A

  • Page 1 SDU AC-A Series A272-290 Rev. 5 07/2018 Uninterruptible Power Supply...
  • Page 2 SDU AC-A Series A272-290 Rev. 5 07/2018 What’s Included The SDU UPS is shipped with the following items: User manual • UPSMON software CD • NOTE: Monitoring/diagnostic software is included on the UPSMON CD. The software is compatible with Windows XP, 7, 8, 10, Server-2000, 2003, 2008 and Linux. PSMON High speed 2.0 Standard Type A-B USB cable, 6 ft (1.8 m) •...
  • Page 3: Table Of Contents

    SDU AC-A Series A272-290 Rev. 5 07/2018 CONTENTS 1.0 Introduction ..... . 1 2.0 Important Safety Instructions ....2 3.0 Installation Instructions .
  • Page 4 SDU AC-A Series A272-290 Rev. 5 07/2018 FIGURES Figure 1: Transition to Back-Up Mode Due to Power Outage . 1 Figure 2: Input/Output Terminals ....3 Figure 3: Mounting the UPS DIN Rail ... . . 3 Figure 4: Front Panel .
  • Page 5: Introduction

    SDU AC-A Series A272-290 Rev. 5 07/2018 1.0 Introduction The SDU AC - A Series is a compact, “Off-Line” DIN rail mountable UPS, which provides conditioned power to sensitive electronic equipment in an industrial environment. It supplies connected equipment with stepped approximation to sinewave input during power outage to simulate the power generated by the utility.
  • Page 6: Important Safety Instructions

    SDU AC-A Series A272-290 Rev. 5 07/2018 2.0 Important Safety Instructions 2.1 Safety Precautions—SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation of the Uninterruptible Power Supply (UPS). Please read all safety, installation, and operating instructions before attempting to install or operate the UPS.
  • Page 7: Installation Instructions

    SDU AC-A Series A272-290 Rev. 5 07/2018 3.0 Installation Instructions WARNING To reduce risk of fire, connect only to a circuit provided with 20A maximum branch circuit overcurrent protection in accordance with the NEC, ANSI/NFPA 70, and the CEC Part 1, C22.1. Bottom View Line...
  • Page 8 SDU AC-A Series A272-290 Rev. 5 07/2018 WARNING Risk of electric shock, disconnect AC main power source before wiring. Ensure proper grounding 4. I/O Wiring: Make sure the UPS and the AC Supply is OFF (disconnected) before installation. Wire the UPS terminals with 90 °C rated copper wire according to the table below.
  • Page 9: Specifications

    SDU AC-A Series A272-290 Rev. 5 07/2018 4.0 Specifications Catalog Number Description SDU 500A SDU 850A SDU 500A-5 SDU 850A-5 INPUT Capacity VA/Watts 500/300 850/510 500/300 850/510 Voltage Vac 120 V + 10%, -20% 230 V +/ -15% 50 or 60 Hz, +/ -10% (auto-sensing) Frequency Harmonic Distortion THD: 42.1%; maximum single harmonic distortion of: 25.6%...
  • Page 10: General Description

    SDU AC-A Series A272-290 Rev. 5 07/2018 5.0 General Description Communication Card Options  SDUCFRELAYCARD          SDUENETIPCARD Figure 4: Front Panel 1. POWER ON/OFF/TEST: ON - To turn the UPS ON, press and release the button for more than 2 seconds until you hear “3 quick beeps”...
  • Page 11: Figure 5: Product Dimensions

    SDU AC-A Series A272-290 Rev. 5 07/2018 7. Input Circuit Breaker: Protection from AC overload and short circuit. 8. USB Port: High speed 2.0 Standard USB Type B Peripheral Communication Port used to establish control and monitoring with UPSMON software. 9.
  • Page 12: System Block Diagram

    SDU AC-A Series A272-290 Rev. 5 07/2018 6.0 System Block Diagram Figure 6: SDU AC - A Series UPS System Block Diagram Page: 8...
  • Page 13: Operating Instructions

    SDU AC-A Series A272-290 Rev. 5 07/2018 7.0 Operating Instructions 7.1 TURNING ON THE UPS • Press the POWER ON/OFF/TEST button for more than 2 second until you hear the “3 quick beeps” and the LEDs turn ON. Note: If utility power is not present, the UPS will be in back-up mode. The load will be powered from the internal batteries until the discharge point is reached.
  • Page 14: Figure 7: Ups Control Panel, Configuration

    SDU AC-A Series A272-290 Rev. 5 07/2018 7.5 GREEN MODE (continued) UPSMON Software: If UPS is connected to a computer with UPSMON software running, the user can change the Green Mode setting. On the UPSMON software screen, “UPS Control Panel” (see Figure 7 below), you can to enable and disable Green Mode Control by clicking the appropriate box highlighted in the figure.
  • Page 15: Diagnostics

    SDU AC-A Series A272-290 Rev. 5 07/2018 8.0 Diagnostics Condition Description LED Diagnostics Alarm UPS in on back-up mode due Slow beeping. UPS sounds until AC BACK-UP MODE YELLOW to AC Loss utility power recovers. Normal condition source AC MODE GREEN No Alarm supplied by AC Mains...
  • Page 16: Battery Back-Up Times

    SDU AC-A Series A272-290 Rev. 5 07/2018 9.0 Battery Back-Up Time The UPS has an internal 12V sealed Valve Regulated Lead Acid (VRLA) rechargeable battery. Models SDU 500A, SDU 500A-5 SDU 850A, SDU 850A-5 VA/Watts 500/300 850/510 Battery YUASA NPW36-12 YUASA NPW45-12 Load Level Approximate Back-Up Time (Minutes)
  • Page 17: Software And Interface

    SDU AC-A Series A272-290 Rev. 5 07/2018 10.0 Software and Interface Power Monitoring Software (UPSMON SOFTWARE) The CD that comes with the UPS contains the UPSMON monitoring/diagnostic software. Install the UPSMON software on your computer. Connect the UPS to your computer via the 2.0 Standard Type A-B USB cable provided.
  • Page 18: Storage

    SDU AC-A Series A272-290 Rev. 5 07/2018 11.0 Storage Ambient temperature range is -15 °C to +45 °C (5 °F to 113 °F). It is recommended to charge the UPS for at least 8 hours then store the UPS covered and upright in a cool, dry location. Remove accessories and disconnect cables connected to the UPS to avoid unnecessary draining of the battery.
  • Page 19 Note that unit specifications are subject to change without notice. Contact Information Website: www.solahd.com Technical Services E-Mail: solahd.technicalservices@emerson.com Warranty Please see the “Terms & Conditions of Sale”. While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 20 The Emerson logo is a trademark and service mark of Emerson Electric Co. Appleton Grp LLC d/b/a Appleton Group. SolaHD is a registered trademark of Appleton Grp LLC. All other marks are the property of their respective owners. © 2018 Emerson Electric Co. All rights reserved. United States...