Omron S8VK-C Manual page 19

Switch mode power supply
Table of Contents

Advertisement

Available languages

Available languages

Item
Efficiency
Voltage range *1
Frequency *1
Input
Current
Power factor
Leakage current
Inrush current (for a
cold start at 25C) *2
Rated output current
Boost current
Voltage adjustment range *3
Ripple & Noise voltage *4 3-phase, 400 VAC input *11
Input variation influence *13
Output
Load variation influence *12
Temperature
variation influence
Start up time *2
Hold time *2
Overload protection
Overvoltage protection
Additional
functions
Series operation
Parallel operation
Output indicator
Withstand voltage
Insulation
Insulation resistance
Ambient operating temperature
Storage temperature
Environment
Ambient operating humidity
Vibration resistance
Shock resistance
MTBF
Reliability
Life expectancy *10
Weight
Construction
Cooling fan
Degree of protection
Harmonic current emissions
EMI
EMS
Approved Standards *6
Standards
Conformed Standards
SEMI
Note: Refer to page 4 for notes 1 to 18.
Power rating
Output voltage
3-phase, 400 VAC input *11
91% typ.
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
450 to 600 VDC
(allowable range: 450 to 810 VDC) *8
50/60 Hz (47 to 63 Hz)
3-phase, 400 VAC input *11
1.2 A typ.
-
3-phase, 400 VAC input
3.5 mA max./1.0 mA typ.
3-phase, 400 VAC input
28 A typ.
20 A
24 A
22.5 to 29.5 VDC (with V.ADJ) (guaranteed)
130 mV p-p max. at 20 MHz of bandwidth
0.5% max.
1.5% max.
3-phase, 400 VAC input
0.05%/C max.
3-phase, 400 VAC input *11
500 ms typ.
3-phase, 400 VAC input *11
20 ms typ.
Yes, automatic reset
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
the input again) *5
Yes (For up to two Power Supplies, external diodes are required.)
Yes (Refer to Engineering Data) (For up to two Power Supplies)
Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
3.0 kVAC for 1 min. (between all input terminals and output terminals) cutoff current 20 mA
2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA
100 M min. (between all output terminals and all input terminals / PE terminal) at 500 VDC
–40 to 70C (However, only startup is guaranteed for between –40C to –25C. (3-phase only))
(Derating is required according to the temperature.) (with no condensation or icing)
–40 to 85C (with no condensation or icing)
0% to 95% (Storage humidity: 0% to 95%)
10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
150 m/s
135,000 hrs min.
10 years min.
1,600 g max.
No
IP20 by EN / IEC 60529
Conforms to EN 61000-3-2 *15
Conducted Emission
Conforms to EN 61204-3 Class B EN 55011 Class B *16
Radiated Emission
Conforms to EN 61204-3 Class B EN 55011 Class B *16
Conforms to EN 61204-3 high severity levels
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd's standards
ANSI/ISA 12.12.01 *7
SELV (EN 60950-1/EN 50178/UL 60950-1)
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
Conforms to F47-0706 (3-phase, 380 to 480 VAC input) *17
480 W
24 V
2
, 3 times each in ±X, ±Y, and ±Z directions
S8VK-T
960 W (768 W *18)
24 V
92% typ.
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
2.1 A typ.
-
3.5 mA max./1.2 mA typ.
40 A at 3-phase (32 A at 2-phase)
48 A at 3-phase (Not possible at 2-phase)
22.5 to 29.5 VDC (with V.ADJ) (guaranteed) *14
90 mV p-p max. at 20 MHz of bandwidth
700 ms typ.
20 ms typ.
2,700 g max.
3