10. TeCHNICAL DATA

Measuring Ranges and Admissible Basic Errors
Measured
value
Current In
1 A
5 A
Voltage L-N
57.7 V
230 V
Voltage L-L
100 V
400 V
frequency
Active power
Reactive power
Apparent power
Power factor Pf
Tangent j
Cosinus j
j
Imported active
energy
exported active
energy
Reactive inductive
energy
Reactive
capacitive energy
THD
*Depending on the setting of tr_u (voltage transformer ratio: 0.1 ... 4000.0
m.q. - error in relation to measured quantity
rng - error relevant to range value
Caution! Correct measurement requires L3 phase voltage higher
than 0.85 Un.

Indication
range*
0,00 ... 1.5 kA
0,00 ... 60 kA
0,0 ... 230.8 kV
0,0 ... 1.012 MV
0,0 ... 1.200 MV
0.0 ... 440 kV
0.0 ... 1.752 MV
0.0 ... 2.000 MV
47.0 ... 63.0 Hz
-9999 MW ...0,00
W
-9999 Mvar ...0,00
var ... 9999 Mvar
0,00 VA ... 9999
MVA
-1 ... 0 ... 1
-1.2 ... 0 ... 1.2
-1 ... 1
-180 ... 180
0 ...99 999 999.9
kWh
0 ...99 999 999.9
kWh
0...99 999 999,9
kVarh
0...99 999 999,9
kVarh
0...100%
and tr_I (current transformer ratio: 1 ... 10000)
Measuring
range
0,005 ... 1,200
A~
0,025 ... 6.000
50 ... 64 V~
195 ... 253 V~
246 ... 300 V~
85 ... 110 V~
340 ... 440 V~
425 ... 520 V~
47,0 ... 63.0 Hz
-1,52 kW ...1,0
W ... 1,52 kW
-1,52 kvar ...1,0
var ... 1,52 kvar
1,0 VA ... 1,52 kVA
-1 ... 0 ... 1
-1,2 ... 0 ... 1.2
-1 ... 1
-180 ... 180
0...100%
L1
L2
L3
S
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
Table 11
Basic
error
±0.2% rng
±0.2% m.q.
±0.5% m.q.
±0.2% m.q.
±0.5% rng
±0.5% rng
±0.5% rng
±1% rng
±1% rng
±1% rng
±0.5% rng
±0.5% rng
±0.5% rng
±0.5% rng
±0.5% rng
±5% rng