Error Codes When Charging Refrigerant; To Fix The Fluorinated Greenhouse Gases Label - Daikin VRV IV RKXYQ8T7Y1B Installation And Operation Manual

Compressor unit for indoor installation
Hide thumbs Also See for VRV IV RKXYQ8T7Y1B:
Table of Contents

Advertisement

5 Installation
3 Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.
4 Do one of the following:
If
The determined additional
refrigerant amount is reached
Too much refrigerant is
charged
The determined additional
refrigerant amount is not
reached yet
Stage 2: Manual charging
(= charging in the "Manual additional refrigerant charge" mode)
Summary – Manual charging:
Refrigerant bottle
Connected to the service port for refrigerant
charge.
This charges to both circuits, and to the
compressor unit's internal refrigerant piping.
Stop valves
Open
Compressor
Operates
5 Connect as shown. Make sure valve A is closed.
p <
p >
A
b
R410A
a
c
a
Weighing scales
b
Refrigerant R410A tank (siphon system)
c
Vacuum pump
d
Refrigerant charge port
A
Valve A
NOTICE
The refrigerant charging port is connected to the piping
inside the unit. The unit's internal piping is already factory
charged with refrigerant, so be careful when connecting
the charge hose.
6 Open all compressor unit stop valves. At this point, valve A
must remain closed!
7 Take all the precautions mentioned in
page 18
and
"7 Commissioning" on page 26
8 Turn on the power of the indoor units, compressor unit and heat
exchanger unit.
9 Activate setting [2‑20] to start the manual additional refrigerant
charge mode. For details, see
page 23.
Result: The unit will start operation.
Installation and operation manual
16
Then
Disconnect the manifold from
the liquid line(s).
You do not have to perform the
"Stage 2" instructions.
Recover refrigerant until the
determined additional
refrigerant is reached.
Disconnect the manifold from
the liquid line(s).
You do not have to perform the
"Stage 2" instructions.
Disconnect the manifold from
the liquid line(s).
Continue with the "Stage 2"
instructions.
d
RDXYQ
"6  Configuration"  on
into account.
"6.1.8 Mode 2: Field settings" on
INFORMATION
The manual refrigerant charge operation will automatically
stop within 30 minutes. If charging is not completed after
30 minutes, perform the additional refrigerant charging
operation again.
INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging refrigerant"  on page  16
solve the malfunction accordingly. Resetting the
malfunction can be done by pushing BS3. You can
restart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
5.6.4

Error codes when charging refrigerant

INFORMATION
If a malfunction occurs:
▪ In case of 5  HP: The error code is displayed on the
user interface of the indoor unit.
▪ In case of 8  HP: The error code is displayed on the
compressor unit's 7‑segments display and on the user
interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
problems based on error codes" on
5.6.5
To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
1
=
f
GWP: XXX
2
=
2
1
+
1
2
=
GWP × kg
=
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO
VRV IV compressor unit for indoor installation
"5.6.4  Error
and
"8.1  Solving
page 28.
a
kg
b
kg
c
d
kg
e
tCO
eq
2
-equivalent
2
RKXYQ5+8T7Y1B
4P408443-1B – 2016.04

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iv rkxyq5t7y1b

Table of Contents