To Connect The Refrigerant Piping To The Compressor Unit - Daikin VRV IV RKXYQ8T7Y1B Installation And Operation Manual

Compressor unit for indoor installation
Hide thumbs Also See for VRV IV RKXYQ8T7Y1B:
Table of Contents

Advertisement

5 Installation
CAUTION
Do not vent gases into the atmosphere.
4 When all gas and oil is recovered from the pinched piping,
disconnect the charge hose and close the service ports.
5 Cut off the lower part of the gas and liquid stop valve pipes
along the black line. Use an appropriate tool (e.g. a pipe cutter,
a pair of nippers).
WARNING
Never remove the pinched piping by brazing.
Any gas or oil remaining inside the stop valve may blow off
the pinched piping.
6 Wait until all oil is dripped out before continuing with the
connection of the field piping in case the recovery was not
complete.
5.3.3
To connect the refrigerant piping to the
compressor unit
NOTICE
▪ Be sure to use the supplied accessory pipes when
carrying out piping work in the field.
▪ Be sure that the field installed piping does not touch
other pipes, the bottom panel or side panel.
1 Remove the service cover. See
unit" on
page 10.
2 Choose a piping route (a or b).
a
To the back
b
To the top
3 If you have chosen the piping route to the top:
Installation and operation manual
12
"5.1.1 To open the compressor
a
a
a
Cut the insulation (under the knockout hole).
b
Hit on the knockout hole, and remove it.
c
Remove the burrs.
d
Paint the edges and areas around the edges using repair
paint to prevent rusting.
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend you
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
4 Connect piping (by brazing) as follows:
5 HP
d
c
a
b
a
Liquid line (circuit 1: to heat exchanger unit)
b
Gas line (circuit 1: to heat exchanger unit)
b
c
Liquid line (circuit 2: to indoor units)
d
Gas line (circuit 2: to indoor units)
1
Pinched piping
2
Piping accessory
3
Field piping
5 Reattach the service cover.
6 Seal all gaps (example: a) to prevent small animals from
entering the system.
a b c d
8 HP
3 1
1
2
2
3
RKXYQ5+8T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1B – 2016.04
d
c
b
a

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iv rkxyq5t7y1b

Table of Contents