Connecting The Electrical Wiring; Field Wiring: Overview; Guidelines When Connecting The Electrical Wiring; To Connect The Electrical Wiring On The Compressor Unit - Daikin VRV IV RKXYQ8T7Y1B Installation And Operation Manual

Compressor unit for indoor installation
Hide thumbs Also See for VRV IV RKXYQ8T7Y1B:
Table of Contents

Advertisement

f
GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO
-equivalent) is used to determine the maintenance
2
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2 Fix the label on the inside of the compressor unit. There is a
dedicated place for it on the wiring diagram label.
5.7

Connecting the electrical wiring

5.7.1

Field wiring: Overview

Field wiring consists of:
▪ Power supply (always including earth)
▪ Communication (= transmission) wiring between the compressor
unit, the heat exchanger unit, and the indoor units.
Example:
380-415 V
220-240 V
3N~ 50 Hz
1~ 50 Hz
a
b
c
d
F1/F2
(16 V)
f
F1/F2
(16 V)
g
a
Main switch
b
Earth connection
c
Power supply wiring (including earth) (sheathed cable)
F1/F2
Transmission wiring (sheathed + shielded cable) (using
shielded cable for the transmission wiring is mandatory for
5 HP, and optional for 8 HP)
d
Compressor unit
e
Heat exchanger unit
f
Indoor unit
g
User interface
Branches
No branching is allowed after branching.
B
A
C
A
Central user interface (etc...)
B
Compressor unit
C
Indoor unit
RKXYQ5+8T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1B – 2016.04
220-240 V
1~ 50 Hz
e
b1
b2
c1
b3
c2
a
D
D
Heat exchanger unit
a
Main line. The main line is the line to which the
transmission wiring of the heat exchanger unit is
connected.
b1, b2, b3
Branch lines
c1, c2
No branch is allowed after branch
5.7.2
Guidelines when connecting the electrical
wiring
Tightening torques
Wiring
Screw size
Power supply wiring
(power supply +
shielded ground)
Transmission wiring
5.7.3
To connect the electrical wiring on the
compressor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located on the switch box cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service covers of the compressor unit and the
switch box.
2 Connect the transmission wiring as follows:
5 HP
RKXYQ5
RDXYQ5
X2M
X2M
TO IN/D
TO OUT/D
F1 F2
F1 F2
a1
a2
a
b
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
a
Sheathed + shielded cable (2 wires) (no polarity)
a1, a2
Connection of shield to earth
b
Terminal board (field supply)
WARNING
Shielded cable. Using shielded cable for the transmission
wiring is mandatory for 5 HP, and optional for 8 HP.
5 HP
RKXYQ5
RDXYQ5
X2M
X2M
F1 F2
a1
a2
a1, a2 Earth (use the screw delivered as accessory)
When using shielded cable:
▪ In case of 5 HP (a1 and a2): Connect the shield to the
earth of the compressor unit and the heat exchanger
unit.
▪ In case of 8  HP (only a2): Connect the shield only to
the earth of the heat exchanger unit.
5 Installation
Tightening torque
(N•m)
M5
2.0~3.0
M3.5
0.8~0.97
8 HP
RKXYQ8
RDXYQ8
X1M (A1P)
X2M
TO IN/D
TO OUT/D
F1 F2
F1 F2
a2
a
b
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
8 HP
RKXYQ8
RDXYQ8
X1M (A1P)
X2M
F1 F2
X1M
a2
Installation and operation manual