Download Print this page

olympia electronics GR-490/ADR Manual page 6

Addressable self testing non-maintained emergency ceiling mounted luminaires

Advertisement

Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Temperature (tc)
TEST
A-1900
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:X: Self contained
0: Non maintained (*)
A: Including test device
B: Including remote test mode
C: Including inhibiting mode
E: With non-replaceable lamp(s)
F: Automatic test gear complying
with IEC 61347-2-7 denoted EL-T
90: 1.5 hour duration
180: 3 hours duration
(*) Non Maintained operation: The luminaire turns on illumination source, only in case of power supply
failure.
ATTENTION!!!
The light source of this luminaire is not replaceable when the light source reaches its end of life
the whole luminaire shall be replaced.
Battery replacement
It can be done only by a competent person and after the mains interruption.
1. Detach the front cover by applying pressure using a flat blade screw driver. Next, unfasten the four
retaining screws without removing them and remove the diffusor.
3. Disconnect the connector and remove the old battery.
4. Connect the new battery with the same type (step 2 of the installation instructions) and place it in
the position of the old one.
5. Replace the removed parts and power the device.
Page 6 from 9
LED MODULE CHARACTERISTICS
GR-490/ADR
GR-491/ADR
Olympia Electronics S.A.
3-3,1V DC
2W
fixed connection between main pcb and led module
Test and Faults Reset operations with the A-1900 card (not
included and available after request).
For lights test, you must place the card in front of the TEST
indicator and remove it immediately.
For Autonomy Test, you must place the card in front of TEST
and hold it for 5 to 10 seconds.
To reset errors you must place the card in front of TEST by
holding it for 10 to 15 seconds and removing it.
X 0
A
B C
E
F
1
8
0
CAUTION : Do not view directly with bare eyes
GR-492/ADR
0405183
65 °C max. across the board
GR-493/ADR
2,8-2,9V DC
1W
923493003_09_001