Waterproof selftesting maintained/non maintained emergency luminaire with wireless communication

Advertisement

Quick Links

Package Contents
1
Luminaire
1
Set of Pictograms
1
Mounting accessories
1
Manual
General
These devices are used indoors and outdoors
the BATTERY FAULT LED will lit and battery needs to be
o
(ta 40 C) in places where emergency light is needed.
replaced. If the result of the test is good then the
Each device must be permanently connected to
luminaire enters charging mode and the CHARGE LED
mains power supply. In normal operation the battery
starts blinking until the battery is fully charged.
is charging. The light source can be either on or off,
Automatic Operational Test
depending on user's choice. In case of a mains power
supply failure, the device enters emergency mode
This test includes all the operations that are provided
and the illumination LED turns on. When the mains
in Manual Operational Test and is conducted
automatically every 15 days and lasts 3 seconds.
power supply is restored the device turns to normal
operation.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6
Autonomy Duration Selection
months and measures the device's back up operation
The user can select one of the 3 available minimum
and emergency duration. This test includes all
autonomy durations 1 hour, 3 hours and 8 hours. The
functions of the Manual Autonomy Test.
selection must be done while the luminaire is
disconnected from AC and battery supplies. The
Wireless communication
selection is achieved through Switches 2 & 3 of DS1
The WL luminaire models have the ability to
as shown below.
communicate over the air with Olympia's control
panels for wireless emergency luminaires. The
luminaires can also communicate with a PC/laptop
through a gateway (Ethernet, Wi-Fi, USB). For more
1 2 3 4
1 2 3 4
1 2 3 4
information, please refer to Wireless Emergency
1h
Lighting guides, available on the company's website.
3h
8h
(default position)
Lens Removal
Technical Label Installation
When the luminaire is used without the pictograms or
Two additional labels are included in the package.
the SP-1100 and you require more light output then
one for 3 hours duration (180) and one for 8 hour
remove the lens that covers the LEDs.
duration (480). Depending on the selected duration,
the installer must cover the default 1 hour (60)
printing with one label that has the required
ΑΤΤΕΝΤΙΟΝ!!!
duration. Please take notice of the orientation of the
1. Operations for installation, maintainance or testing
label.
must be done by authorized personnel only.
2. Always use in any case round mains cable, with a
Manual Operational Test
diameter of 5-10mm (H05RN-F type 2x1mm² or
Remove the diffusor and then by pressing the test
any other type, at least equal to it's mechanical
button briefly an operation test is initiated. The light
and electrical properties). ATTENTION!! The cable
source and the emergency circuit of the device are
must not be deformed in any way (This
tested. The manual test can be conducted only if the
requirement is important to ensure the ΙΡ rating).
mains power supply and the battery are connected.
3. The device must be connected to the mains power
During this test period the LAMP TEST LED will blink.
supply through a circuit breaker that is depends
The battery must have adequate charge. This test
on the total line's power load.
lasts for 3 seconds.
4. In case of battery replacement, it must be replaced
by the same type, by the manufacturer or a
Manual Autonomy Test
competent person.
A duration test can be conducted by pushing the button
5. In case of inactive use for a period greater than 2
steadily for 5 to 10 seconds. In order to be performed,
months, disconnect the battery by pulling out the
the mains power supply should be connected and the
battery's connector.
battery should be fully charged. The luminaire enters
6. I s not allowed to discard batteries into common
t i
emergency mode, the CHARGE LED is turned OFF and
trash bins, they must be discarded only
the BATTERY FAULT LED starts blinking. Its duration is
battery recycling points. Do not incinerate.
the stated autonomy duration of the luminaire. If at the
end of the test the autonomy is lower than the nominal,
Indications LED Status
LAMP
BATT.
CHARGE
Description
FAULT
FAULT
(green)
(red)
(yellow)
Charging
Fully charged
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
1
Installation Instructions
1
3
2
1
4
Drill one of the 5 available holes with a 16-18mm drill bit. Install the included rubber gasket and pass
through the power cables. Install the included tie (if needed) to fasten and securely the power cables.
5
6) Autonomy Duration Selection
(Read on General Informations, Page 1)
6
7 b) Non-Maintained Operation
N
L
in
Ν for neutral, L for live wire WARNING!! Isolate the mains power supply before making the connections.
7
Battery Connection
Note:
Permanently
ON
Blink
Off
8
Indifferent
2
923100402_09_001
2
A
B
4
3
5
7 a) Pernament Maintained Operation
N
L
or
Link
1 2 3 4
Switch number 4 of DS1
must be in ON position.
Ν for neutral, L for live wire
WARNING!! Isolate the mains power supply before making the connections.
7
7 c) Controlled Maintained Operation of the lamp
N
L
External
and
and
switch
1 2 3 4
Switch number 4 of DS1
Switch number 4 of DS1
must be in OFF position.
must be in OFF position.
8
9
923100402_09_001
Attention!! The 6 plastic
latches (A) must be secured
(click
requirement is important to
ensure the IP65 rating.
Power on the luminary.
10
Pictogram Installation
A
2 2
1 1
Mounting Methods
Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations, special
accessories are included.
Wall
bottom
Wall installation
view
Extra Mounting Methods *
* ATTENTION!!! The below mounting methods can be done after request of the necessary
mounting accessories!!
Suspended installation with A-3018 accessory
The luminary can be installed in a suspended
ceiling.
1 2 3 4
A marking panel (SP-1100) can be installed on the luminary pointing the desired direction.
Ceiling installation
with marking panel
NOTE!!
After finishing the installation you must power the luminaire for at least 24 hours in order to
completely charge the battery. The rated autonomy duration can be achieved after that time.
3
sound).
This
11
2
1
1. Fit the pictogram you need to the diffuser, be careful to
secure it on the 3 plastic holders.
2. Refit the diffusor with the pictogram.
Ceiling
Ceiling installation
Suspended ceiling installation
with mounting accessory
A-3018
Suspended ceiling installation
with mounting accessories
and marking panel
923100402_09_001

Advertisement

loading

Summary of Contents for olympia electronics OLY-1004

  • Page 1 Package Contents Installation Instructions Attention!! The 6 plastic Luminaire latches (A) must be secured Set of Pictograms (click sound). This Mounting accessories Manual requirement is important to ensure the IP65 rating. General Power on the luminary. These devices are used indoors and outdoors the BATTERY FAULT LED will lit and battery needs to be (ta 40 C) in places where emergency light is needed.
  • Page 2 Wireless Non Maintained operation: The luminaire lights its illumination source, only in mains power supply’s Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the failure. buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the NOTE!! The installer should fill in, on the specification label, the letter G if the luminaire is used as a buyer the transportation cost.

This manual is also suitable for:

Oly-1004wpOly-1004wl