Specifications - Toshiba TOSVERT VF-FS1 Series Function Manual

Lonworks option unit - communication function manual
Hide thumbs Also See for TOSVERT VF-FS1 Series:
Table of Contents

Advertisement

8. Specifications

Item
Number of domains
Number of address
entries
Number of alias tables
Communication
transceiver
Baudrate
Protocol
Communication signal
Transmission distance
Functional block
Number of
Network variables
Number of connected
nodes
Service pin function
Terminal block
Specification
2
37
8
Free topology transceiver
TP/FT-10 channel type.
78kbps
LonTalk
2 wires plus shield
Free topology:
Between devices: 400m or less
Total cable length: 500m or less
Bus topology ( both terminated):
Total cable length: 1400m or less
Stub length: 3m or less
Node Object (0)
Variable Speed Motor Drive (1)
Input network variables: 8
Output network variables: 17
Configuration properties: 12
64 nodes at maximum
Mechanical switch (SW2)
Detachable terminal block 3-pole
- 37E -
Notes
ANSI/EIA/CEA 709.3
ANSI/EIA 709.1
NETA, Sheild, NETB
When recommended cable is used:
Level 4/22AWG
L
M
functional profile
ON
ARK
Variable Speed Motor Drive
However, a host and routers are
counted as one node.
Used for notification of Neuron ID to
the host.
Applicable terminal block
Manufacturer: PHOENIX CONTACT
Type-Form : MSTB 2,5/3-ST-5,08
E6581373