3.7. Reference parameter of the inverter

Reference parameter of the inverter is listed below.
Title
acc
dec
fh
ul
ll
vl
cmod
fmod
f111 ...
f603
f800
f801
f803
f829
f851
For LIU007Z, set up "Communication error trip function (f803, see the inverter
instruction manual for details)" to stop the inverter when this option unit is deactivated
by an unusual event such as tripping, an operating error, power outage, failure, etc.
Mandatory
Deactivated option unit may cause an accident, if the "Communication error trip
function" is not properly set up.
Name
Acceleration time
Deceleration time
Maximum frequency
Upper limit frequency
Lower limit frequency
Base frequency 1
Command mode selection
Setpoint mode selection
Logic input terminal function
Emergency stop selection
Communication baud rate
Communication parity
Communication error trip time
Communication protocol
Operation at network disconnection
Description
Do not change these parameters, because
the L
W
ON
Network command has priority when the
inverter is Remote mode. (See previous
section)
Network setpoint has priority when the
inverter is Remote mode. (See previous
section)
Set proper value if use (See the inverter
instruction manual).
For "nviEmergOverride"
Set "1" (default)
Set "1" (default)
Set properly value
Set "1" (MODBUS)
See "section 7.4 Communication health
management".
Warning
- 11 -
option unit using them.