6.4.9. nciRampDownTm (Ramp Down Time)

Configuration property, Variable Speed Drive 6010_11 (Mandatory)
SNVT type: SNVT_time_sec (107)
SCPT reference: SCPTrampDownTm (161)
It determines the ramp down time of the motor.
- Valid range: 0.1 to 3200.0 sec.
- Unit: 0.1 sec.
- Default value: 10.0 sec.
N.B.: By editing this variable, this option unit changes the inverter parameter "dec" automatically.

6.4.10. nciDrvSpeedScale (Default value for nviDrvSpeedScale)

Configuration property, Variable Speed Drive 6010_11 (Optional)
SNVT type: SNVT_lev_percent (81)
SCPT reference: SCPTdefScale (162)
It is used as the default value for "nviDrvSpeedScale". When this option unit is initialized, it will be
updated.
- Valid range: -163.840 to 163.830%
- Unit: 0.005%
- Default value: 100.000%

6.4.11. nciPwUpOutTm (Power up delay time).

Configuration property
SNVT type: SNVT_time_sec (107)
SCPT reference: SCPTpwrUpDelay (72)
It defines the time until starting transmission after the device powered up. It is useful to improve network
traffic at power-up.
- Valid range: 0.0 to 300.0 sec (If the value exceed 300.0, the value is limited to 300.0 sec)
- Unit: 0.1 sec.
- Default value: 0.0 sec.