Operating the UPS

Battery Backup Time and Discharge Process

the UpS batteries provide about 5-7 minutes of back-up time depending on the 1600ep unit kVa rating.
these times are valid when the unit is operating under full load and at the rated power factor. the exact
length of these times will depend on the UpS model used, condition of the batteries, amount and type of
load, temperature and other variables. See battery backup time in 'Standard Specifications' beginning on
pages 15-20.
the following illustration graphically shows the battery discharge process at full load conditions.
CURRENT
I
MAx
I
MIN
Battery Low Voltage Tolerances
excessive discharge will cause the UpS battery voltage to drop. the chart shown below lists the voltage
level at which each UpS low-voltage alarm will sound and at what level the low-voltage condition will
cause the unit to automatically shut down.
UpS Capacity
nominal voltage (Vnom)
alarm voltage (Vlow)
Shutdown voltage (Vmin)
1600ep Series instruction manual
VOLTAGE
V
NOM
V
LOW
V
MIN
100%
BATTERY CAPACITY
3.6 kVa-
3.6 kVa
6 kVa
rohS
144 Vdc
216 Vdc 216 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc
130 Vdc
192 Vdc 192 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc
114 Vdc
170 Vdc 170 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc
SHUTDOWN
20%
0%
8 kVa
10 kVa
14 kVa
18 kVa
22 kVa