Devicenet Local/Remote Operation - Toshiba DEV002Z Instruction Manual

Devicenet option
Hide thumbs Also See for DEV002Z:
Table of Contents

Advertisement

6. DeviceNet Local/Remote Operation

The example below shows how to configure the VF-AS1/PS1 for local / remote operation.
<Terminal function>
F terminal ............ Operating command
R terminal............ DeviceNet/Local (Terminal in this example) switching
RR/S4 terminal.... Operation frequency command
<Wiring>
Variable resistor for adjustment
<Parameter setting>
cmod (Command mode selection) = 0 (Terminal board)
fmod (Frequency setting mode selection 1) = 2 (RR/S4)
f112 (Input terminal selection 2 (R)) = 48 (Remote/Local control)
<Operation>
R-CC terminal open:
R-CC terminal closed:
1 -
10k ohm
Operation command
DeviceNet/Local
Switch
VF-AS1/PS1 is controlled as slave device of DeviceNet.
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the RR/S4 signal input.
- 18 -
E6581295⑥
VF-AS1/PS1
PP
RR/S4
CCA
SW1
F
SOURCE
SINK
R
CC