Changing Device Configuration (Using Dip Switches); Changing System Family (Ar/Ap Switching) - EUCHNER MGB-L0 AR Series Operating Instructions Manual

Safety systems
Hide thumbs Also See for MGB-L0 AR Series:
Table of Contents

Advertisement

Operating Instructions Safety Systems
MGB-L0...-AR.-... and MGB-L0...-AP.-...
11.6.

Changing device configuration (using DIP switches)

Tip!
You will find an animation on device configuration at www.euchner.com.
DIP switches
The devices can be configured using the DIP switches. The following settings are possible:
Ì

Changing system family (AR/AP switching)

Position of the switches
Item
Description
1
DIP switches
2
Sticker with factory setting
Function of the switches
Important!
DIP switches 3, 4 and 6 must be set to "off" position.
Detail
Switch
Function
A
1+2
On: Device is operated as AP system
Off: Device is operated as AR system
B
3+4
No function
C
5
On: Configuration possible
Off: Configuration inhibited (factory setting)
D
6
No function
11.6.1. Changing system family (AR/AP switching)
CAUTION
Malfunction due to incorrect configuration or incorrect connection.
Ì
Note that the terminal assignment also changes on changing the configuration (see chapter 11.8.
Terminal assignment and contact description on page 26).
1. Switch off power supply.
2. Set DIP switches 1, 2 and 5 as shown.
For changing from AR => AP
ON
1
2
3. Switch on power supply for 5 s.
The change is confirmed by the illumination of the Power LED. All other LEDs are off.
¨
4. Switch off power supply and set DIP switch 5 to OFF.
The next time the device is started, it operates in the operating mode set.
¨
24
3 4
5
6
For changing from AP => AR
ON
1
(translation of the original operating instructions) 2112657-13-05/18
ON
1
2 3 4 5 6
A
2
3 4
5
6
1
2
B
C D