Notes about

Important!
Ì
For use and operation as per the
class 2 circuits" must be used. The same requirement applies to the safety outputs.
Alternative solutions must comply with the following requirements:
a) Electrically isolated power supply unit with a max. open-circuit voltage of 30 V/DC and a limited
b) Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be
Ì
The mounting of conduits directly on the MGB is not allowed. Cables are allowed to be connected
only via suitable cable glands. For this purpose use EUCHNER cable gland of type EKPM20/06U.
Equivalent cable glands can be used if they are UL-listed (QCRV) and are suitable for the related
cable diameter (22 AWG – 17 AWG).
1) Note on the scope of the UL approval: Only for applications as per NFPA 79 (Industrial Machinery).
The devices have been tested as per the requirements of UL508 (protection against electric shock and fire).
11.2.

Safety in case of faults

Ì
The operating voltage UB is reverse polarity protected.
Ì
The safety outputs FO1A/FO1B are short circuit-proof.
Ì
A short circuit between FI1A and FI1B or FO1A and FO1B is detected by the device.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
11.3.

Fuse protection for power supply

The power supply must be provided with fuse protection depending on the number of devices and current required for the
outputs. The following rules apply:
Max. current consumption of an individual device I
I
= I
+ I
+ I
max
UB
UA
I
= Device operating current (80 mA)
UB
I
= Load current of monitoring outputs OD, OT and OI (3 x max. 50 mA) + switches
UA
I
= Load current of safety outputs FO1A + FO1B (2 x max. 50 mA)
FO1A+FO1B
Max. current consumption of a switch chain Σ I
AR
Σ I
= I
max
FO1A+FO1B
n
= Number of connected devices
Current assignment to the fuses
Current
I
UB
I
FO1A+FO1B
I
UA
22
current of max. 8 A.
designed for max. 3.3 A and should be integrated into the 30 V DC voltage section.
FO1A+FO1B
+ n x (I
+ I
)
UB
UA
requirements
, a power supply with the feature "for use in
1)
max
max
Fuse circuit F1
80 mA
(2 x max. 200 mA)
(translation of the original operating instructions) 2112657-13-05/18
Fuse circuit F2
I
= (3 x max. 50 mA)
OD,OT,OI
I
= max. 100 mA
switches
(per switch)
I
= max. 5 mA
indicators
(per indicator)