11.4.
Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì
On the usage of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connection cables:
Parameter
Conductor cross-section, min.
R max.
C max.
L max.
11.5.
Notes on cable laying
Lay all MGB connection cables in a common cable harness.
MGB-L.-...
UB 0V UA 0V
FI1A/
FO1A/
FI1B
FO1B
+ 24 V DC
0 V
Important: lay cables in a common harness
Figure 14:
Stipulated cable laying
2112657-13-05/18 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L0...-AR.-... and MGB-L0...-AP.-...
Value
0.13
60
120
0.65
PLC
cabinet
Unit
mm²
W/km
nF/km
mH/km
EN
23