Introduction of AMF10/16 control module 
Introduction of iL‐MRS10/16 controller panel as follow 
 
1. Start‐up. Start the engine. 
2. Stop. Stop the engine. 
3. Reset. Clean failure and alarm state. 
4. Horn reset. deactivates the horn 
5.  Mode  left.  Change  the  generator  set  mode 
left‐handed (MEASUREMENT‐AUTO‐MAN‐OFF) 
6.  Mode  right.  Change  the  generator  set  mode 
left‐handed. (OFF‐MAN‐AUTO‐MEASUREMENT) 
7. Generator set power on/off. Manual turn on/off the 
generator set power switch 
8. Generator set failure: red LED starts flashing when 
generator set failure occur. After fault reset button 
is  pressed,  goes  to  steady  light  (if  an  alarm  is  still 
active) or is off (if no alarm is active) 
9.  Generator  set  voltage  present:  green  LED  is  on,  if 
gen voltage is present and within limits 
10. Connect generator set power present. Green LED 
light, generator set output switch is on, otherwise 
the green LED flash. 
11.  Page.  Cyclic  selection  of  the  display  mode 
(measurement adjustment) 
12.  Up.  Select  the  set  point,  select  the  screen  or 
increase set value point 
13.  Down.  Select  the  set  point,  select  the  screen  or 
decrease set value point 
14. Enter. Confirm the set point value 
Introduction of function and operation 
MRS10/16  self‐start  control  module  is  low  a  level  to 
AMF20/25  control  module,  it  is  a  single  module 
without  mains  power  measurement  function,  and 
also  has  less  I/O  terminals  than  AMF20/25.  Besides, 
their  other  function  and  operation  are  similar  or 
same. 
 
 
 
 
 
 
 
3.7
 ATS control panel 
3.7.1 ATS panel general introduction 
Our  customer  will  need  this  ATS  if  generator  set  is 
used for self‐start standby power. In order to achieve 
full  automatic  transfer  between  mains  power  and 
generator  set  power  to  guarantee  all  load  present, 
our ATS panel select the best ATS for all generator set. 
And  to  the  most  possibility  to  serve  our  customers' 
demand, we prepare two types of ATS: MRS and AMF. 
Besides  MRS  and  AMF  can  be  jointed  to  a  double 
standby ATS after a little change, which is used for 2 
 
generator sets work together stand by mains power. 
Please  reference  relevant  details  of  ATS  for  its 
function, application, operation and so on. 
 
 
 
 
 
Safty Attention:   
! We are very pleasure for your support of our product, 
before  you  use  our  ATS  please  read  this  instruction 
carefully. 
We  mark  three  attention  parts  in  accordance  with 
different situation: 
Danger:   
! If you do wrong action, Personal death or other big 
disaster must be happened. 
 
Moving Attention 
Danger :   
!  When  you  move  ATS  by  crane  or  elevator,  don't 
stand beneath the ATS, to avoid personal death. 
 
Installation Attention   
Attention: 
! All operators must be professional electrician. 
! Cut off all power before installation. 
! Fix screw in accordance with TORPUE standard. 
! Place ATS on plane in vertical direction. 
! Don't install ATS in the environment, where are high 
temperature, humidor or filled with corrosion gas. 
! Connect neutral pole with "N" pole while you install 
4poles of ATS. 
 
Operation Attention 
Danger:   
!  Don't  connect  energized  main  circuit  or  control  line 
with terminal. 
Attention:   
! If ATS is tripping, cut off power source, find problem 
and solve it at first. 
Our  company  supply  ATS  panel  should  use  for  AMF 
series  generator  control  module,  from  the  diagram 
you can see it is very easy to connect cable and easy 
install  ATS  panel.  Our  panel  can  use  in  AUTO  or 
16
User manual