Hyundai DHY22KSEm Operation And Maintenance Manual

Hyundai DHY22KSEm Operation And Maintenance Manual

Soundproof type diesel genset, 22kva 50hz

Advertisement

Quick Links

SOUNDPROOF TYPE DIESEL GENSET
DHY22KSEm
DHY22KSEm
RATED POWER (kW/kVA)
RATED POWER (kW/kVA)
MAX. POWER (kW/kVA)
MAX POWER (kW/kVA)
FREQUENCY (Hz)
VOLTAGE (V)
CURRENT (A)
CONTROLLER
ATS PORT
GENERATOR SET
BATTERY (Ah)
FUEL TANK CAPACITY (L)
COOLING FLUID VOLUME (L)
FUEL CONSUMPTION (l/h 50/100% loading)
RUNNING TIME UNDER (h 50/100% loading)
NOISE LEVEL BEHIND 7 METERS (dBA)
ENGINE MODEL
POWER OUTPUT (kW/1500rpm)
ROTATE SPEED
SPEED REGULATION
ENGINE
STARTING METHOD
DISPLACEMENT (cc)
OIL CAPACITY (L)
ALTERNATOR
RATED POWER (kW/kVA)
ALTERNATOR
POWER FACTOR (Cosφ)
VOLTAGE REGULATION
LOW OIL PRESSURE
BLOCK ON START UP
LOW BATTERY
HIGH TEMPERATURE ON WATER
ALARMS
LOW OIL LEVEL
LOW RUNNING ON ENGINE
EMERGENCY STOP
N.G. (kg.)
G.W. (kg.)
PRODUCT DIMENSIONS (mm)
LOGISTICAL DATA
CAPACITY (units/container)
RECOMMENDED SPARE PARTS
REF.
SPARE PARTS NAME
AIR FILTER CORE
OIL FILTER ELEMENT
TURBO OIL FILTER ELEMENT
FUEL FILTER ELEMENT
22kVA 50Hz.
22kVA 50Hz.
D
D
Diesel generator SOUNDPROOF type, powered by 4 cylinders 4 stroke water cooled
ie
d
d
direct injection engine with electric start, for Industrial applications, large fuel tank
ire
p
p
providing over 8 hours running, AVR for smooth voltage output, large muffler to reduce
ro
n
n
noise harmful effects, Bottom fuel tank, air preheating system for easy start up (we
oi
recommend water heater for cold weather). Two bottom holes for the forklift and two
r
r
ec
h
h
hooks on the cover top. Digital control panel, Emergency stop button, fuel intake hole
oo
o
o
outside the canopy, weather proof canopy.
ut
DESCRIPTION:
D200/300/400. ELECTRIC STARTER MOTOR
REFERENCE:
7016005
QUANTUTY: 1
QTY
1
1
-
1
20/20
22/22
50
230
87
IL-NT MRS10
INCLUDED
1x12V-54Ah
93
10
4.5/7.7
21/12
68
DG4100
27
1500 RPM
MECHANICAL
ELECTRIC
3.298
15
InteliLite
184G
21/21
1
AVR / BRUSHLESS
YES
MRS 10
YES
YES
MANUAL AND REMOTE
START CONTROLLER
YES
YES
YES
YES
PIN PASSWORD
880
RS232/485 INTERFACE
2220X950X1300
FAULTS REPORT
6/20GP;12/40GP;12/HQ
MULTI-LANGUAGE FUNCTION
OPTIONAL ACCESSORIES
REF.
ACCESSORIES NAME
ATS BOX & 30m cables: ATS1-100A
WATER HEATER 1000W
INTELLIGENT BATTERY CHARGER 24V
24 HOURS FUEL TANK
* Product might be different from pictures shown
* specifications might vary as continuous product development
MEASUREMENTS
GENERATOR VOLTAGE
GENERATOR CURRENT
GENERATOR FREQUENCY
POWER FACTOR
OIL PRESSURE
COOLANT TEMPERATURE
BATTERY VOLTAGE
ENGINE ROTATING SPEED
ENGINE HOURS RUN
BREAKER
MCB (0~125A)
MCCB (125~1000A)
POWER OUTPUT AREA
TERMINALS U.V.W.N.PE
3 X SINGLE PHASE SOCKETS
NT
InteliLite
NT
MRS 10
MRS 16
Mode
Mode
Start
I
Horn
Fault
Stop
reset
reset
0
Page
Page
G
Enter
Enter
MRS 16
MANUAL AND REMOTE
START CONTROLLER WITH
SUPPORT FOR EFI ENGINES
MRS10
YES
OPTIONAL
NO
YES
Mode
Mode
Start
I
Horn
Fault
Stop
reset
reset
0
G
I
/
0
MRS16
YES
OPTIONAL
YES
YES
QTY
1
1
1
1

Advertisement

Table of Contents
loading

Summary of Contents for Hyundai DHY22KSEm

  • Page 1 SOUNDPROOF TYPE DIESEL GENSET DHY22KSEm DHY22KSEm 22kVA 50Hz. 22kVA 50Hz. Diesel generator SOUNDPROOF type, powered by 4 cylinders 4 stroke water cooled direct injection engine with electric start, for Industrial applications, large fuel tank providing over 8 hours running, AVR for smooth voltage output, large muffler to reduce noise harmful effects, Bottom fuel tank, air preheating system for easy start up (we recommend water heater for cold weather).
  • Page 2 DIESEL GENERATOR Models Hyundai Engine Series Operation and Maintenance manual...
  • Page 3 SAFETY. The operator of the machine; Is responsible for and has a duty of care in making sure that the machine is operated safely and in accordance with the instructions in this user manual. Should never leave it in a condition, which would allow an untrained or unauthorised person/s to operate this machine.
  • Page 4 Carbon monoxide Carbon monoxide is a colourless and odourless gas. Breathing it can cause death as well as serious long-term health problems such as brain damage. The symptoms of carbon monoxide poisoning can include the following; Headaches, Dizziness, Nausea, Breathlessness, Collapsing or Loss of Consciousness.
  • Page 5 Petrol safety. Always fuel and defuel in well-ventilated area. Always wear correct, suitable and fit for purpose Personal Protective Equipment (PPE), suggested items are as follows, but are not limited to. Hand protection. Protective clothing. Respiratory protective equipment. When defueling always use a propriety fuel retriever. Always carry fuel in the correct and clearly marked container.
  • Page 6 If acid gets into your eyes, you should remove it immediately. Make sure that you do not wash the acid to another part of the face or body. Gasses from charging batteries are highly flammable. You must charge in well-ventilated areas. Additional Safety Instructions.
  • Page 7 Safety and Warning  Before operation and maintenance for the generator sets, please read carefully about this manual and make sure a  good understanding of this operation manual and other documents which attached with the engine.  Correct installation of the generator set is the precondition of normal operation. Qualified spare parts shall be used  for maintenance to ensure good running condition and long life expectancy of the generator sets.  The generator set shall be operated only by the staffs who have received training on the operation and the repair  shall be made by the authorized staffs. Operator and maintenance staff shall be clear about safety and preventive  actions and operation maintenance procedure.  The  generator  sets  can  only  be  started under  safety  conditions. Please  do  not start  the  generator sets  when  any  abnormal condition has been found so that to avoid accidents.  When clean, maintain and repair the generator sets, please shut down the generator set and cut off the connection  of negative polar of the battery or dismantle battery connecting cable, and place warning label at the relative place  so that to avoid accident.  The  exhaust air  discharged  from  engine is  harmful  for  people’s  health.  All  of  the  generator sets  installed  indoors  shall discharge the exhaust gas to outside doors. ...
  • Page 8 Safety labels information  TRANSPORT WARNING  !  Never  lift  the  generating  set  by  attaching  to  the  engine  or  alternator  lifting  lugs,  instead  use  the  lifting points on the base frame or canopy.  !  Ensure  that  the  lifting  rigging  and  supporting  structure  is  in  good  condition  and  has  a  capacity  suitable for the load.  !  Keep  all  personnel  away  from  the  generating  set  when it is suspended. ...
  • Page 9 CHEMICAL WARNING  !Ensure  that  the  generating  set  room  is  properly  ventilated.  !Keep  the  room,  the  floor  and  the  generating  set  clean. When  spills of fuel, oil, battery electrolyte or  coolant  occur,  they  should  be  cleaned  up  immediately.  ! Never store flammable liquids near the engine.  !Do  not  smoke  or  allow  sparks,  flames  or  other  sources  of  ignition  around  fuel  or  batteries.  Fuel  vapors ...
  • Page 10: Table Of Contents

    Table of Contents 2.11 Power distribution system………………………11 1 General Introduction 3 Operation 1.1 Brief Introduction……………………………………1 3.1 Inspect Before Operation ………………………12 1.2 Generator Set Main Parts Specifications …………1 3.2 Generator set’s running …………………………12 1.4 Alternator ……………………………………………1 3.3 After Running ……………………………………13 1.3 Diesel Engine ……………………………………… 1 3.4 Record for running ………………………………13 1.4 Alternator ……………………...
  • Page 11: General Introduction

    User manual  General Introduction   Brief Introduction  HYUNDAI  series  diesel  engine  generator  sets  is  the  core  products  of  HYUNDAI  Power  Equipment  Manufacturing  Co.,Ltd.  Thanks  to  their  good  performance,  the  generator  sets  are  widely  used  in  the  fields  of  construction,  communication,  banking  business,  mining,  leasing  industry  and  other  special ...
  • Page 12: Cooling System

    ◆Before being assembled, rotors need to pass dynamic   Control Panel  balance  testing.  The  improved  damper  reduces  voltage deviation and heat under unstable load.  All  models  of  HYUNDAI  Power  generator  sets  use  ◆The  exciter  rotor  output  is  fed  to  the  main  rotor  high grade control panel. The core of control panel is  through  a  three  phase  full  wave  bridge  rectifier,  the  an  imported  digital  diesel  engine  control  module, ...
  • Page 13: Others

    User man nual lso  it  can  p revent  the  generator  s ets  from  be eing  1.10.2  Lubr icant discha arge hole wh hich directly y  amaged by c cold winter w weather!  connect to   outside  Our  gener rator  sets  have  been    facilitated    with  lubricant  di ischarge  valv ve ...
  • Page 14: Installation

    User manual ◆Ensure foundation’s levelness and smoothness.  ◆If possible, waste discharge sink can be sued so that  Installation the  waste  oil  can  be  discharged  in  a  timely  manner.  Cable channel for generator power output cable need   General Outline  to be reserved.  ◆Normally, concrete foundation is reliable, simple and  Correct  installation  of  generator  set  is  the  preferable.  When  pouring  the  concrete  foundation,  precondition which ensure the normal working status  please make sure the surface of concrete is flat, and  of the generator set. The working room for generator  no  scratch  is  allowed.  Gradienter  or  similar  set ...
  • Page 15: Installation Of Generator Set

    User manual 1~1.5  m  of  distance  from  the  generator  set  and  Soft connection is needed to connect the parts of the  1.5~2m above the generator set.  generator  set  to  outside.  For  example:  corrugated  ◆The  generator  set  working  room  shall  be  furnished  vibration  reduction  pipe  has  been  used  to  connect  exhaust  pipes,  air  exhaust  path,  fuel  inlet  pipe,  fuel  with ...
  • Page 16 User manual and side stress.  ◆ Reserve  some  space  for  hot  shrinkage  and  cold  expansion.  ◆Reserve space for generator set vibration.  ◆Reduce exhaust noise level.  Overload  of  exhaust  backpressure  will  cause  following adverse effect:  ◆Output power loss  ◆Fuel efficiency reduce  ◆Exhaust gas temperature rise  Note:  When  more  than  one  generator  set  are  installed,  try  not  to  discharge  all  of  the  generator  sets’  gas  from  one ...
  • Page 17: Cooling System

    Engine’s  coolant  shall  have  three  functions  listed  as  expectancy of generator set.  below:  ◆Provide enough heat transmission capacity  Note:  ◆ Prevent  all  metal  material  and  sealing  material  HYUNDAI  Power  can  provide  customers  with  overall  within  the  cooling  system  from  corrosion(Cave  sound proof generator set.  corrosion)  ◆Provide sufficient anti‐freeze capacity   Cooling system  Warning: ...
  • Page 18: Lubricant System

    HYUNDAI  is  only  responsible  for  installation  coolant  if  needed.  The  coolant  which  needs  to  be  of  the  internal  fuel  system  which  includes  fuel  tank ...
  • Page 19 User manual The  following  fuel  oil  specification  is  typical.  For  a  specific  engine  refer  to  manufacturers’  data  sheets  2.8.2  Fuel tank  for fuel oil details.  Our generator sets provide base frame style fuel tank  Fuel Recommended Physical Properties Feature  for  customer.  The  base  frame  style  fuel  tank  is  Viscosity    installed  with  fuel  tank,  fuel  pipes  and  fuel  level  1.3 to 5.8 centistrokes (1.3 to 5.8mm per second) at 40°C (104°F) ...
  • Page 20: Battery

    User manual below 10 meters, this fuel inlet pipe’s inside diameter  controlled locally by manual, and also can be started  shall  be  at  least  20%  bigger  than  that  of  the  hose  or stopped by remote control (controlled by external  installed  in  this  engine.  Fuel  return  pipe  shall  be  signal line) users are required to correctly connect the  connected  to  the  top  of  fuel  tank.  Don’t  directly  signal  line  to  this  control  panel.(details  see  the  connect it to fuel inlet pipe. ...
  • Page 21: Electrical Connection

      temperature.  Method  of  installation,  proximity  of  Note:  other cables, etc. All connections should be carefully  HYUNDAI  Power  series  diesel  engine  generator  sets  checked for integrity.  require  users  to  safely  connect  generator  sets  and  Current carrying capacity of power cables that will be  base frames to the ground, please refer to the ground  given  in  APPENDIX  A.  On  the  other  hand,  there  is  a ...
  • Page 22: Operation

    User manual       3.2.3  Start  Operation     Part  of  the  generator  set  control  panel  has  been  furnished with idle speed / full speed transfer switch,  3.1  Inspect Before Operation  users can choose if the engine need to be started in  idle speed or in one time full speed. Usually the time  After  finished  installation,  our  diesel  engine  period  for  idle  speed  shall  not  exceed  five  minutes.  generator  set  can  be  put  into  use.  Each  time  before  Do ...
  • Page 23: After Running

    User manual malfunction  or  power  distribution  malfunction.  down etc.  Please  press  down  the  emergency  stop  on  the  control panel, so that to immediately shut down the  Only  when  the  correct  and  complete  record  for  generator set. Under normal condition, please do not  running  (maintenance)  has  been  kept  very  well,  the  use emergency stop to stop the generator set.  user  can  get  correct  and  excellent  after  sales  (warranty) service. ...
  • Page 24: Operation For Control System

    User manual During the generator sets group running, please keep  watching  to  avoid  the  generator  sets  group  stop  running  because  of  individual  generator  set’s  malfunction.     Operation for control system  3.6.1  Generator control panel operation  Our  generator  set  standard  supply  two  different  control  module:  one  is  single  generator  with  remote  start  function,  the  other  is  single  generator  with  Automatic Mains Failture (with ATS panel) . ...
  • Page 25 User manual control/measure/monitor  generator  set  through  When  the  power  supply  LED  is  light  means  AMF  computer.  The  AMF20/25  panel  has  a  LCD  to  display  controller  is  active,  then  user  can  select  operation  generator  set  parameters,  and  has  type (OFF/MAN/AUTO/MEASUREMENT)  OFF/MAN/AUTO/MEASUREMENT mode.  A. OFF mode  Start; stop; mains power on/off; generator set power ...
  • Page 26: Ats Control Panel

    User manual  ATS control panel  3.7.1 ATS panel general introduction  Our  customer  will  need  this  ATS  if  generator  set  is  used for self‐start standby power. In order to achieve  full  automatic  transfer  between  mains  power  and  generator  set  power  to  guarantee  all  load  present,  our ATS panel select the best ATS for all generator set.  And  to  the  most  possibility  to  serve  our  customers’  demand, we prepare two types of ATS: MRS and AMF. ...
  • Page 27 User manual MANUAL status.      Manual status operation:  Step 1    You should check the generator control module set in  MANUAL  status,  then  use  the  operate  handle  insert  the switch axis.      Step 2    Operating direction of the arrow    No              MODEL    1                ATS switch  2 ...
  • Page 28: Maintenance

    User manual For  each  50~600  hours  of  running  or  at  least  each  12  Maintenance months  ! Change lubricant and lubricant filter  4.1  General outline  ! Because the quality of lubricant oil, sulfur content of  the  fuel,  and  lubricant  consumption  rate  of  each  For  different  types  of  generator  sets,  users  need  to  engine  is  different,  the  interval  for  lubricant  oil  refer ...
  • Page 29: Alternator

    User manual Please  do  not  use  the  battery  to  start the  generator  4.3  Alternator  set  under  low  temperature  because  the  battery  Inside  and  outside  of  the  alternator  shall  be  cleaned  capacitance  can  not  output  normally  under  low  periodically.  And  the  frequency  of  cleaning  depends  temperature, ...
  • Page 30: Check For Malfunction

    User manual   Check for Malfunction    5.1  General outline  There  are  many  factors  which  may  cause  the  generator set’s malfunction, and the malfunctions are  usually  closely  related  to  each  other.  This  section  mainly  summarize  and  list  the  possible  malfunctions  of general diesel generator sets. This is just for user’s  reference  when  they  try  to  eliminate  the  malfunction(s).  (Especially  important  for  new  generator set’s customer) ...
  • Page 43 APPENDIX G Maintenance Record Maintenance Time: Generator set model: Engine model: Alternator Model: Generator set serial No.: Engine serial No.: Alternator serial No.: Accumulated running hours: Maintenance cycle: Reasons for maintenance (periodic maintenance or malfunction maintenance) Inspection and repair Inspection and adjustment Change of parts Clean and maintenance Others...
  • Page 44 APPENDIX H...