Field settings table
Breadcrumb
Field code
Setting name
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
9.C.1
[C-02]
Bivalent
9.C.2
[7-05]
Boiler efficiency
9.C.3
[C-03]
Temperature
9.C.4
[C-04]
Hysteresis
Installer settings
9.D
[C-09]
Alarm output
9.E
[3-00]
Auto restart
9.F
[E-08]
Power saving function
9.G
Disable protections
└─ Overview field settings
9.I
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.I
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.I
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.I
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.I
[0-04]
--
9.I
[0-05]
--
9.I
[0-06]
--
9.I
[0-07]
--
9.I
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
9.I
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
9.I
[0-0D]
High ambient temp. for DHW WD curve.
9.I
[0-0E]
Low ambient temp. for DHW WD curve.
9.I
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.I
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.I
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.I
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.I
[1-04]
--
9.I
[1-05]
--
9.I
[1-06]
--
9.I
[1-07]
--
9.I
[1-08]
--
9.I
[1-09]
--
9.I
[1-0A]
What is the averaging time for the outdoor temp?
9.I
[1-0B]
What is the desired delta T in heating for the main zone?
9.I
[1-0C]
What is the desired delta T in heating for the additional zone?
9.I
[1-0D]
--
9.I
[1-0E]
--
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[2-05]
Room antifrost temperature
9.I
[2-06]
Room frost protection
9.I
[2-09]
Adjust the offset on the measured room temperature
9.I
[2-0A]
Adjust the offset on the measured room temperature
9.I
[2-0B]
What is the required offset on the measured outdoor temp.?
4P629095-1B - 2022.05
Range, step
Default value
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0: No
1: Bivalent
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: Normally open
1: Normally closed
R/W
0: No
1: Yes
R/W
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
8
12
35
20
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
1
1
20
35
22
18
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
5
5
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
4~16°C, step: 1°C
12°C
R/W
0: Disabled
1: Enabled
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
Installer setting at variance with