ERGA04~08E + EHVZ04+08S18+23E
Daikin Altherma 3 R F
4P629093-1B – 2022.05
Reheat setpoint
Desired reheat tank temperature, used:
▪
in Schedule + reheat mode, during reheat mode: the guaranteed minimum
tank temperature is set by the Reheat setpoint minus the reheat hysteresis.
If the tank temperature drops below this value, the tank is heated up.
▪
during storage comfort, to prioritize the domestic hot water preparation. When
the tank temperature rises above this value, domestic hot water preparation and
space heating/cooling are executed sequentially.
#
Code
[5.4]
[6-0C]
Schedule
You can set the tank temperature schedule using the schedule screen. For more
information about this screen, see
Heat up mode
The domestic hot water can be prepared in 3 different ways. They differ from each
other by the way the desired tank temperature is set and how the unit acts upon it.
#
Code
[5.6]
[6-0D]
See the operation manual for more details.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
[5.7.1]
[2‑01]
Description
Reheat setpoint:
▪
30°C~min(50,[6‑0E])°C
"10.4.3 Schedule screen:
Description
Heat up mode:
▪
0: Reheat
only: Only reheat operation is
allowed.
▪
1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪
2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
Description
Activation:
▪
0: No
▪
1: Yes
10
Configuration
|
4
Example" [
137].
Installer reference guide
175