Page 12
3.6
3.6
C C C C
3.6
3.6
OMPATIBLE
OMPATIBLE
OMPATIBLE
OMPATIBLE
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible with
the AFP2800 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium batteries
is not recommended.
Manufacturer
Best and Best
Best and Best
Best and Best
NOTE:
The batteries could be seriously and permanently damaged if they are permitted to discharge below 20V DC when placed
in series.
3.7
3.7
3.7
3.7
S S S S
YSTEM
YSTEM
YSTEM
YSTEM
Base System
Item
Communications Ring 1
8 System Outputs

Power Supply

2 Local AZF's
2 RS232 comms ports
Keyboard Interface
System Memory
System Expansion
Item
Ring Expander –
Communications Ring 2
Loop Interface Module –
FlashScan 
Panel Expansion Relays
© N
I
P
OTIFIER
NERTIA
TY
www.PDF-Zoo.com
B B B B
Type
Number
Sealed LA
BP17-12
Sealed LA
BP24-12
Sealed LA
BP40-12
C C C C
APACITY
APACITY
APACITY
APACITY
Description
RS485 communications ring to support
Up to 100 Field Modules
Up to 99 Annunciators
Bell Output
Warning System Output
General Alarm Output
5 Additional programmable relay
outputs
3 Amp power supply and battery
charger
Fused 24VDC outputs
AZF 1
AZF 2
Laptop interface
System event printer
PS2 QWERTY IBM PC keyboard
7500 Named points
5000 Control scripts
4000 History events
Description
Second RS485 communications ring to
support
Up to an additional 100 Field Modules
Ring expander module to
communicate with up to 5 x pairs of
Notifier LCM/LEM modules. ie: total of
10 loops of FlashScan.
Up to an additional 8 IFS-803 8-way
relay boards can be added via the
panel serial relay port
L
, 2001
TD
firealarmresources.com
AFP-2800 - Fire Indicator Panel – System Description
ATTERIES
ATTERIES
ATTERIES
ATTERIES
Voltage
12
12
12
A A A A
E E E E
ND
ND
ND
ND
Capacity (Ah)
Qty Required
17
24
40
XPANDABILITY
XPANDABILITY
XPANDABILITY
XPANDABILITY
Notes
A larger power supply
will be required if total
module load exceeds
2.5A. Power supplies up
to 18A are available.
Notes
Each loop of
FlashScan supports
159 Analog/Addressable
Detectors and 159
Addressable Modules
.
WWW
INERTIA
2
2
2
.
.
COM