7.1.- General technical specifications.
INPUT
Single phase voltage ................................................................... 120V, 220V, 230V, 240V.
Three phase voltage .................................................................... 208V, 220V, 230V, 240V, 380V, 400V, 415V + N + E.
Voltage range .............................................................................. +33% / -8% nominal voltage.
Frecuency From ............................................................................ 48 to 63Hz.
Protection per phase ................................................................... Single pole circuit breaker.
OUTPUT
Single phase voltage ................................................................... 120V, 220V, 230V, 240V.
Three phase voltage .................................................................... 208V, 220V, 230V, 240V, 380V, 400V, 415V + N + E.
Accuracy ...................................................................................... better than ±2%
Soft start voltage ........................................................................ 210V.
Minimum saving voltage .............................................................. 188V (phase to neutral ).
Control ......................................................................................... Independent per phase.
Harmonic distortion ...................................................................... Nil.
Efficiency ...................................................................................... >97%.
Permissible load power factor ...................................................... from 0,5 lagging to 0,7 leading.
Unbalancing between phases ..................................................... Permissible 100%.
Saving voltage selection 1 or 2.................................................... Through dipswitches per phase.
BYPASS
Included and automatic and solid state and independent
per phase .................................................................................... Yes.
ENVIRONMENT
Operating temperature ................................................................ from -40ºC to +45ºC.
Relative humidity ......................................................................... from 0% to 95%, non-condensing.
Maximum operating altitude ....................................................... 2.400 m.a.s.l.
Mean Time Between Failures (MTBF) ......................................... 60.000 hours.
Mean Time To Repair (MTTR) ..................................................... 30 minutes.
Acoustic noise at 1 meter ............................................................ <35dB.
INDICATIONS
Optical (per phase) ...................................................................... Process «Mode»
Acoustic (per phase) ................................................................... Automatic and solid state Bypass alarm.
+4% / -29% saving voltage 1.
+10% / -2,4% savinf voltage 2.
Saving order activated «Saving ON».
Selected tap.
Automatic and solid state Bypass .
Automatic and solid state Bypass alarm.
- 27 -