Salicru DC POWER-L Series User Manual

Salicru DC POWER-L Series User Manual

Thyristor-controlled charger rectifier 25.. 800 a
Hide thumbs Also See for DC POWER-L Series:

Advertisement

Quick Links

UNINTERRUPTIBLE POWER SUPPLIES (UPS) + STABILISERS - STEP-DOWN LIGHT DIMMERS (ILUEST) + POWER SOURCES + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + LINE VOLTAGE STABILISERS
DC POWER SUPPLY DEVICE.
THYRISTOR-CONTROLLED CHARGER RECTIFIER 25.. 800 A.
DC POWER-L Series
USER MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Salicru DC POWER-L Series

  • Page 1 UNINTERRUPTIBLE POWER SUPPLIES (UPS) + STABILISERS - STEP-DOWN LIGHT DIMMERS (ILUEST) + POWER SOURCES + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + LINE VOLTAGE STABILISERS DC POWER SUPPLY DEVICE. THYRISTOR-CONTROLLED CHARGER RECTIFIER 25.. 800 A. DC POWER-L Series USER MANUAL...
  • Page 2 USER MANUAL...
  • Page 3 7.1. Look after your safety. 7.2. Considerations to take into account. 7.3. Earth connection, terminal or strip (X5) and/or (X5A). 7.4. Connection of the system to the cabinet or battery bank. Terminals (X11) - (X12) and (X47) - (X48). SALICRU...
  • Page 4 Salicru is pro- hibited, with the company fully and exclusively reserving its ownership rights over it.
  • Page 5: Safety Information

    SALICRU...
  • Page 6 Quality assurance and standards. 3.1. Statement by the management. 3.3. Environment. Our goal is customer satisfaction, therefore this Management has This product has been designed to respect the environment and manufactured in accordance with ISO 14001. decided to establish a Quality and Environment Policy, through the implementation of a Quality and Environmental Management System that will enable us to comply with the requirements de- Recycling of the device at the end of its useful life:...
  • Page 7 The illustrations in Fig. 2, 4, 5 and 6 are representative of the DC-50-L 24 650 x 615 x 2120 range of standard models in the DC Power-L series. They reflect DC-75-L 24 the external and internal physical arrangement of each of the two...
  • Page 8 DC-25-L 125 650 x 615 x 1320 DC-50-L 125 650 x 615 x 2120 DC-75-L 125 DC-100-L 125 650 x 815 x 2120 DC-150-L 125 650 x 815 x 2120 1 + 1 DC-200-L 125 DC-250-L 125 DC-300-L 125 DC-350-L 125 850 x 815 x 2120 DC-400-L 125 DC-450-L 125...
  • Page 9 ) opc. (F/Q10) (X37) (F/Q1A) (F/Q3) (F/Q2) For single phase + - + - R-S-T (PR) (PR) (PR) Fig. 2. Front view of rectifier cabinet with closed and opened front door (PF) measuring 650 x 615 x 2120 mm. SALICRU...
  • Page 10 (CT) (PC) Fig. 3. Front view of rectifier cabinet with closed front door (PF) measuring (650 & 850) x 815 x 2120 mm. USER MANUAL...
  • Page 11 (TC) ) opc. (X37) (F/Q10) (F/Q1A) (F/Q8) (F/Q2) For single phase R-S-T (PR) (PR) (PR) Fig. 4. Front view of rectifier with open front door (PF) measuring (650 & 850) x 815 x 2120 mm. SALICRU...
  • Page 12 (CT) (PC) Fig. 5. Front view of rectifier cabinet with closed front door (PF) measuring 650 x 915 x 2120 mm. USER MANUAL...
  • Page 13 (TC) ) opc. (F/Q1A) (F/Q8) (F/Q2) Fig. 6. Front view of rectifier cabinet with opened front door (PF) measuring 850 x 915 x 2120 mm. SALICRU...
  • Page 14 (CT) Fig. 7. Front view of battery cabinet with closed and opened front door (PF) measuring (650 & 850) x 815 x 2120 mm. USER MANUAL...
  • Page 15: Dimensional Drawings

    ˆ The device can operate with PbCa or NiCd batteries, ei- ther sealed or with maintenance. Unless indicated other- wise, they should be PbCa sealed. Fig. 9. Fig. 8. Cabinet dimensions 650 x 615 x 2120 mm Cabinet dimensions 650 x 815 x 2120 mm. SALICRU...
  • Page 16 Fig. 11. Cabinet dimensions 850 x 915 x 2120 mm. Fig. 10. Cabinet dimensions 850 x 815 x 2120 mm. USER MANUAL...
  • Page 17 Anchor points for securing the base to a solid surface. (F/Q8) Disconnector fuse for battery protection of the two Only in cabinets with removable battery trays. poles (+) and (–), located in the accumulator cabinet. (PC) Control panel with LCD display. (2) (3) (4) SALICRU...
  • Page 18 (PF) Front door of rectifier and/or battery cabinet. (PI) Lifting elements -feet- (optional). (PR) Wall bushings for cable routing. (R103) Temperature/battery float voltage sensor. (RN) Slot for connection cable routing. (RV) Ventilation grilles. Screws for fixing the terminal cover (TB). Screw for fixing the protective cover (TC).
  • Page 19 Number of branches in parallel of the type 2 battery. Disre- gard when there is only one battery branch of each type. Number of branches in parallel of the type 1 battery. Disre- gard for 1 and only one type of battery. Device series. Rectifier SALICRU...
  • Page 20: Block Diagram

    Rectifier block diagram and description. 5.1. Block diagram. Input Input prot. Input AC / DC converter LC filter Non-return Rectifier Output Output filter switch transformer (Rectifier) diode output prot. switch filter Control / Display Battery Batteries prot. Communications Fig. 12. Block diagram. 5.2.
  • Page 21: Output Filter

    The semiconductor temperature control and overtemperature shutdown system provides added protection by reducing the need for device interventions in the event of abnormal operation, since it protects the most important part of the system, preventing SALICRU...
  • Page 22 failure and saving on possible expensive repairs. Once the battery recharges, the device will automatically go to float mode. For the protection of personnel, it also has isolation failure detec- tion, which provides an alarm if a potentially dangerous situation The duration of the quick charge will be proportional to the dis- arises.
  • Page 23 To avoid premature ageing of the battery due to long periods of float charging without discharging, quick charging can be acti- vated manually via the control panel (with timed stopping) and periodically (with timed activation) to restore the full charge of the battery. SALICRU...
  • Page 24: Reception And Unpacking

    Device reception. 6.1. Reception and unpacking. • To unpack the device, follow the steps in Figure 11. • On reception of the device, check that it has not been dam- aged during transportation. If it has been damaged, notify ˆ Cut all of the polyester straps ‘’ and remove the corners your supplier or, in their absence, our company.
  • Page 25 Regardless of the type of accumulators used in a device, the design life of the batteries is regulated by the official Euro- pean body EUROBAT, taking into account, among other char- acteristics or conditions, temperature, float voltage, number of charging and discharging cycles, depth of discharge, etc. SALICRU...
  • Page 26: Installation

    Installation. • Supplied with this user manual and included in the same • Finally, it is obligatory to leave the cover or covers of documentation CD is the EK266*08 ‘Safety instructions’ the cabinet(s) in position and the front door closed document.
  • Page 27 DC Power-L. • It is advisable, and so required by the regulations or legisla- • Any handling and connection of the batteries should tion of the country, to connect the device to earth. SALICRU...
  • Page 28 Make sure that all of the device’s loads are only connected to Battery terminals in rectifier cabinet. earth in the form of a terminal or strip (X5). Failure to limit the earthing of the loads to this single point would create earth Battery terminals in return loops and degrade the quality of the power supplied.
  • Page 29: Floating Output

    It is recommended to distribute the output on different lines block pin arrangement. and each with protection elements (disconnectors with fuses or circuit breakers), to be installed by the customer and of single pole in the negative pole type. SALICRU...
  • Page 30 7.10. Optional electrolyte level sensor, fier cabinet and connected at its opposite end (X25A) through wall bushings (PR) located on its base and in- terminal (X25A). sert it into the battery cabinet through the respective wall bushings (PR) located on its base. Connect the two hose cables (MD) interchangeably •...
  • Page 31: Shutdown Procedure

    If the following alarm message appears on the control panel display... PHASE ROTATION ERROR .. an audible alarm will also sound and the device will not be able to start, as the input phase sequence will be in- correct. SALICRU...
  • Page 32: Control Panel

    Control panel. 9.2. Basic functions of the keys and notes of interest. LCD display. (b) (a) ‘ENT’ key. ‘ESC’ key. Forward key ‘ ’. Backward key ‘ ’. Right key ‘ ’. Left key ‘ ’. • Use the forward ‘ ’...
  • Page 33 () twice. Use key () to access the screens of the different Screen 4.5 sub-menus and move freely from one to the other by means of This alarm appears when the device’s output voltage is below a keys () and (). certain value. Screen 2.1 SALICRU...
  • Page 34 Screen 4.6 Screen 4.25 This alarm appears when the device’s battery voltage is above This alarm appears when the voltage of the input line is below its a certain value. minimum value. Screen 4.7 Screen 4.26 This alarm is displayed when the device’s battery voltage is This alarm indicates that the device’s output switch is open.
  • Page 35 Use to consult and modify the batteries’ maximum quick charging Use to set the isolation failure alarm threshold. time. ** Password-protected screens. Screen 5.10 Use to consult and modify the batteries’ manual charging time. Screen 5.11 ** Use to consult and modify the batteries’ periodic charging time. SALICRU...
  • Page 36 9.3.8. ‘Password’ menu. To access this menu from the home screen, press the forward key () seven times. ** Password-protected screens Screen 7.1 By entering the password on this screen, you can access the parameter settings of the batteries and rectifier of the previous sections.
  • Page 37 Screen 6.2 Screen 6.3 For single-phase devices on Screen 1.8 and 1.12, the voltage and input cur- * PASSWORD * rent are shown. [0000] Password-protected screens. Enter password on Screen 7.1. Screen 7.1 Fig. 19. Control panel screens map. SALICRU...
  • Page 38 Alarm Activation condition Deactivation condition Category Delay (s) 1) Not exceptional charging: For 125V > 137.5 V rated output Manual reset using the quick/exceptional Output voltage high alarm 2) Exceptional charging: Urgent, Vout Not OK charging buttons. For 125V > 137.5 V rated output For 125V rated, Vout >...
  • Page 39: Maintenance

    Technical Service and Support (TSS). Among other advantages, it will streamline any regulatory procedures for the intervention of TSS in the event of a fault. SALICRU...
  • Page 40: General Technical Specifications

    11. Annexes. 11.1. General technical specifications. INPUT COMMUNICATION AND ALARMS Slot Yes, one pre-connected as standard Single-phase 230 V AC (3 wire: 1 phase + N + TT) SNMP / Remote maintenance NIMBUS, optional AC voltage (V) Three-phase 3x230 or 3x400 depending on DB9 connector (COM1) Optional model (4 wire: 3 phases + TT)
  • Page 41 IRED (infra-red emitting diode). • Circuit breaker.- A circuit breaker is a device capable of in- terrupting the electrical current of a circuit when it exceeds certain maximum values. SALICRU...
  • Page 42  : ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ USER MANUAL...
  • Page 43  : ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ SALICRU...
  • Page 44 BARCELONA Tel. +34 93 848 24 00 902 48 24 00 (Only Spain) Fax. +34 94 848 11 51 salicru@salicru.com Tel: (T.S.S.) +34 93 848 24 00 902 48 24 01 (Only Spain) Fax. T.S.S. +34 93 848 22 05 sst@salicru.com...