Salicru DC POWER-L DC-75-L 12P 110V EE671774-1 Manual

Dc power supply device, thyristor-controlled charger rectifier 12 pulse

Advertisement

Quick Links

UNINTERRUPTIBLE POWER SUPPLIES (UPS) + STABILISERS - STEP-DOWN LIGHT DIMMERS (ILUEST) + POWER SOURCES + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + LINE VOLTAGE STABILISERS
DC POWER SUPPLY DEVICE.
THYRISTOR-CONTROLLED CHARGER RECTIFIER 12 PULSE.
DC POWER-L Series 12 pulse
DC-75-L 12P 110V EE671774-1
MANUAL EE671774-1

Advertisement

loading

Summary of Contents for Salicru DC POWER-L DC-75-L 12P 110V EE671774-1

  • Page 1 UNINTERRUPTIBLE POWER SUPPLIES (UPS) + STABILISERS - STEP-DOWN LIGHT DIMMERS (ILUEST) + POWER SOURCES + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + LINE VOLTAGE STABILISERS DC POWER SUPPLY DEVICE. THYRISTOR-CONTROLLED CHARGER RECTIFIER 12 PULSE. DC POWER-L Series 12 pulse DC-75-L 12P 110V EE671774-1 MANUAL EE671774-1...
  • Page 2 USER MANUAL...
  • Page 3 Reception and unpacking. 6.2. Packing list and contents. 6.3. Storage. Installation. 7.1. Look after your safety. 7.2. Considerations to take into account. 7.3. Earth connection, terminal or strip 7.4. Connection of the system to the cabinet or battery bank. SALICRU...
  • Page 4 Salicru is pro- hibited, with the company fully and exclusively reserving its ownership rights over it.
  • Page 5 SALICRU...
  • Page 6 Quality assurance and standards. 3.3. Environment. 3.1. Statement by the management. This product has been designed to respect the environment and Our goal is customer satisfaction, therefore this Management manufactured in accordance with ISO 14001. has decided to establish a Quality and Environment Policy, through the implementation of a Quality and Environmental Man- agement System that will enable us to comply with the require- Recycling of the device at the end of its useful life:...
  • Page 7 The device will however be delivered with proper labelling, to which full attention will need to be paid. Fig. 1. View of the control panel. SALICRU...
  • Page 8 Locking Lifting eyebolts Protective methacrylate LCD synoptic panel COLD START button Input circuit breaker (Q1) Output circuit breaker (Q2) Battery circuit breaker (Q3) Input terminals R, S, T Alarm interface X32 (see Table 2) Interface Aux. Contacts X34 (refer to Table 3) Port RS 485 Temperature probe Output terminals...
  • Page 9 ˆ The device can operate with PbCa or NiCd batteries, ei- ther sealed or with maintenance. Fig. 3. Cabinet dimensions 623 x 803 x 2056 mm SALICRU...
  • Page 10 4.1.2. Nomenclature. Rectifier. 2/DC-100-L 110-1/2x9AB147/213-3x220E COM EE553000 Rectifier with particular specifications. COM Potential-free contacts extended version. Optional electrolyte level detection. 3x220 Rated input voltage. Disregard for 3x400V. /213 Last three digits of the code of the type 2 battery. Last three digits of the code of the type 1 battery. Letters of the battery family.
  • Page 11 For greater versatility, the system can be either single-phase or the system as self-protection for the device. three-phase. Regardless of the topology of the mains, protection elements are installed against voltage peaks that could come from the mains. SALICRU...
  • Page 12 5.2.6. Battery. (*) The relay table corresponds to the extended COM ver- sion (relays from 1 to 9). The device will function as a stand-alone power source even The standard relays included on the control board are 10, 11, 12 when the AC input mains fail, supplying voltage to the load con- and 13.
  • Page 13 100% of the capacity transferred during the specified discharge cycle in a maximum period of 12 hours, with the charger simulta- neously powering 100% of the loads. SALICRU...
  • Page 14 5.3.2. Charging type priorities. Considerations The battery is considered to be charged when there is a lack of Table 3 below shows the established charging type priorities: mains voltage and it is capable of giving a complete cycle and, at the end of it, the operating voltage is not lower than the minimum Type Priority...
  • Page 15 We recommend the site. keeping the packaging for possible future use.                    Fig. 5. Unpacking process. SALICRU...
  • Page 16 • For devices ordered with a pallet and/or eyebolts, both only Before using a device with batteries in which the backup is on request, proceed as follows: determined by accumulators, for the first time or after a long period of time without use (maximum 6 months), it is neces- ˆ...
  • Page 17 Before physically installing the accumulators, check that the protections or disconnectors of the system are in the ‘Off’ po- sition, especially that of the batteries of the device (Q3) and its counterpart (Q8) in the battery cabinet, when there is an external accumulator bank. SALICRU...
  • Page 18 When the protection consists of fuses, these are supplied If the batteries are connected to the device and its protec- already inserted into the fuse holder base, as the batteries tions are set to ‘On,’ it is irrelevant whether or not the DC themselves are not delivered already installed in the cabinet.
  • Page 19 Since the fuses of the disconnectors are supplied al- ready installed to prevent them from being lost or mis- laid, it is important to check that the disconnectors are open (Off). SALICRU...
  • Page 20 7.6.1. Floating output. • Connect the loads or busbar to the output terminals, re- specting the colour of the cables (red for positive and black for negative) and the polarity indicated on the labelling of the device. • Connect the load or loads to the earth terminal or strip. •...
  • Page 21 ‘Off.’ Swap two of the phases on the input terminals and repeat the startup process described so far. • Set general two-pole output switch (Q2) to ‘On.’ The system is operational. • Start the loads. SALICRU...
  • Page 22 Control panel. 9.2. Basic functions of the keys and notes of interest. LCD display. (b) (a) ‘ENT’ key. ‘ESC’ key. Forward key ‘ ’. Backward key ‘ ’. Right key ‘ ’. Left key ‘ ’. • Use the forward ‘ ’...
  • Page 23 Screen 1.5 INPUT FREQ TEMPERATURES ºC   x x.x Hz DIS: x x BAT: x x    Screen 1.6 Screen 1.7 * SWITCHING * FORCED QUICK  CHARGING: YES   Screen 2.1 Screen 2.2  SALICRU...
  • Page 24 * PARAMETERS * LANGUAGE MODBUS   * USERNAME * SPANISH ADD: 1 19000Bd      Screen 3.1 Screen 3.2 Screen 3.3  * ALARMS * CURRENT LEAKAGE ELECTROLYTE HIGH OUTPUT LOW OUTPUT     ...
  • Page 25 For single-phase devices, the alarm corresponds to the voltage be- Optional extra. tween the phase and the neutral (RN) and, for three-phase devices, between the RS phases. Alarms only available for three-phase devices (ST and TR phases). Table 7. Alarm activation/deactivation conditions. SALICRU...
  • Page 26 Screen 5.9 RELAY ASSOCIATED ALARMS Use this screen to set the minimum time the battery must remain RELE 1: (AC Input failure) Input overvoltage. Input undervoltage. at float before allowing a battery test to be initiated. Input switch open. AC input failure. Screen 5.10 Phase rotation error.
  • Page 27 By entering the password on this screen, you can access the parameter settings of the batteries in the previous menu. Enter the password in the space between the brackets. In the adjacent 4-character field, the type or correlated user name will be displayed. SALICRU...
  • Page 28 10. Maintenance. 10.1. Basic maintenance guide. 10.2.2. Exclusions. Our company will not be bound by the warranty if it notices Batteries and capacitors must be replaced at the end of their ser- that the defect in the product does not exist or was caused by vice life.
  • Page 29 Quality and environmental ISO 9001 and ISO 14001 management Batteries (in external cabinet) Fuses Certification company General output switch Disconnector Soft start (11) Power degradation from +40ºC. (12) No batteries. (13) Power degradation from 1000 masl Table 9. General specifications. SALICRU...
  • Page 30 11.2. Glossary. • AC. Alternating current is electric current in which the mag- nitude and direction vary cyclically. The waveform of the most commonly used alternating current is that of a sine wave, since this achieves a more efficient transmission of energy. In certain applications, however, other periodic waveforms are used, such as triangular or square.
  • Page 31  : ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ SALICRU...
  • Page 32 SISTEMAS DE ALIMENTACIÓN ININTERRUMPIDA (SAI)+ ESTABILIZADORES-REDUCTORES DE FLUJO LUMINOSO (ILUEST) + FUENTES DE ALIMENTACIÓN + ONDULADORES ESTÁTICOS + INVERSORES FOTOVOLTAICOS + ESTABILIZADORES DE TENSIÓN DE LÍNEA Avda. de la Serra, 100 08460 Palautordera BARCELONA Tel. +34 93 848 24 00 salicru@salicru.com Tel. (S.S.T.) +34 93 848 24 00 sst@salicru.com SALICRU.COM OFFICES AND TECHNICAL SERVICE AND SUPPORT CENTRES (T.S.S.)