Download Print this page

DSC CFP-102 Manual

Fire alarm control panel calculation for standby battery requirement
Hide thumbs Also See for CFP-102:

Advertisement

Quick Links

CFP-102 / CFP-105
CFP-102 / CFP-105
Fire Alarm Control Panel
Calculation for Standby Battery Requirement
Step
1
CFP-102 /
CFP-105
2
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
3
NAC 1
NAC 2
4
CFP-200
CFP-205
CFP-500
CFP-161
Pol. Rev.
CFP-161
Mun. Box
CFP-160
(Note 2)
5
AUX+ (5)
6
Total 'standby' and 'alarm' current:
7
Divide 'standby' mA and 'alarm' mA by 1000:
8
Select 'standby' time required (24 or 60 Hr.):
9
Standby Amp-Hr. - multiply 7 × 8 = (Amps × Hr.):
10
Select 'alarm' time required (5 min. = .08 Hr.):
11
Alarm Amp-Hr. - multiply 7 × 10 = (Amps × Hr.):
12
Total Amp-Hr = standby Amp-Hr (9) + alarm Amp-Hr. (11):
13
Multiply the total Amp-Hr. by the safety margin:
14
Total battery Amp-Hr required to support the system:
NOTES:
1. Select a battery with an Amp-Hr. rating that is equal to or larger than the calculated minimum Amp-
Hr. battery required. Note: The maximum battery allowed is 12 Ah.
2. For the relay module, add 8 mA as 'Standby' for each relay programmed for 'Trouble' and add 8 mA
as 'alarm' for each relay programmed for 'alarm'.
3. The Class A modules do not add any 'Standby' or 'alarm' current above that calculated for each zone.
4. When the CFP-161 is used as a Polarity reversal transmitter, add the current draw of the remote
receiver input in the 'standby' mode.
5. For panels used in a 'Remote Station' application (60 Hr. standby), the dialer may be
installed but no current may be drawn from the AUX+ output.
Current per
Device
device (mA)
Standby:
90 / 130
Alarm:
365 / 415
Standby:
Alarm:
60
Standby:
Alarm:
60
Standby:
Alarm:
60
Standby:
Alarm:
60
Standby:
Alarm:
60
Alarm:
Alarm:
Standby:
15
Alarm:
15
Standby:
15
Alarm:
25
Standby:
33
Alarm:
60
Standby:
20 (Note 4)
Alarm:
35
Standby:
20
Alarm:
20
Standby:
0
Alarm:
24
Standby:
Alarm:
Number
Total Standby
of device
Current (mA)
x
1
= 90 / 130
x
1
=
x
=
x
1
=
x
=
x
1
=
x
=
x
1
=
x
=
x
1
=
x
=
x
1
=
x
=
x
=
x
x
x
x
x
x
x
x
x
x
x
=
x
x
=
x
=
mA
Amp
Hr.
× 1.20
Total Alarm
Current (mA)
365 / 415
60
mA
Amp
Amp-Hr.
Hr.
Amp-Hr.
Amp-Hr. Total
Amp-Hr.

Advertisement

loading

Summary of Contents for DSC CFP-102

  • Page 1 CFP-102 / CFP-105 CFP-102 / CFP-105 Fire Alarm Control Panel Calculation for Standby Battery Requirement Current per Number Total Standby Total Alarm Step Device device (mA) of device Current (mA) Current (mA) CFP-102 / Standby: 90 / 130 = 90 / 130...
  • Page 2 © 2001 Digital Security Controls Ltd., Toronto, Canada • www.dsc.com Technical Help Desk (Canada & US): 1-800-387-3630 • Printed in Canada • 29005851 R001...

This manual is also suitable for:

Cfp-105