Power supplies of the indoor and the outdoor units are to be respectively connected to a Residual Current operated Circuit-Breaker
(RCCB) with threshold of 30mA. For inverter driven units (outdoor unit), it is advisable the use of type B residual current device for 3Ph
power supplies and type B or F for 1Ph power supplies (depending on the electrical system to which it is connected). For the units
without inverter, (indoor units) a type A Residual current device is sufficient. The type of connection must in any case be carried out in
a workmanlike manner by qualified personnel in compliance with the national regulations in force.
INTERNAL UNIT
Electrical supply
Admitted voltages field
Rated power input
Max current
Cutout - Circuit breaker size
Differential Circuit Breaker size (RCCB)
Supply cable dimensions *
Signal cable EDF, AFR, PV
EBUS 2 cable
* Cable length < 20m
Note: It is strongly recommended to separate the supply cables from the communication cables.
Note: To avoid interference problems in the connection between the EBUS 2 cable from the internal unit to the external unit, use a shielded cable.
66 / GB
FS - 1 ZONE
V - ph - Hz
230 - 1 -50
400 - 3 -50 230 - 1 -50 400 - 3 -50 230 - 1 -50
V
196 ÷ 253
340 ÷ 440
kW
4
A
19.1
12 - C type
A
25 - C type
12 - C type
mA
Reference
Min. cables
3G6
section
Max diameter
18
[mm]
Recommended
3G6
cables section
Max diameter
18
[mm]
mm
2
mm
2
FS - 2 ZONE
196 ÷ 253
340 ÷ 440
4
4
4
9.6
19.1
9.6
12 - C type
25 - C type
13 - C type
30 - A type
H07RN-F
5G2.5
3G6
5G2.5
17
18
17
5G4
3G6
5G4
19.9
18
19.9
H05RN-F 2 x 0.75 mm
H05RN-F 2 x 0.75 mm
FS L - 1 ZONE
400 - 3 -50
196 ÷ 253
340 ÷ 440
6
6
30
9.6
12 - C type
32 - C type
13 - C type
3G6
5G2.5
18
17
3G6
5G4
18
19.9
2
2