Mode 5 - Pressurising - PEDROLLO E1 MONO Original Instructions For Use

Multifunction electric control panel for electric pumps.
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 36
MODE 5 – PRESSURISING
4-20
mA
Amperometric
pressure
transducer
4-20 mA
Water detection via cosφ (dry running) and pump management via
pressure transducer
The pressure transducer controls operation of the two pumps, turning them
on or off according to the value measured in the system. The cosφ of the
pumps will also be monitored to generate a dry running alarm when ap-
propriate.
If the pressure drops to P (read)<(P1-ΔP1), either one pump or the other
starts running according to the alternating logic and the control panel then
checks the cosφ.
If the following control logic has been selected:
– DRY LOGIC=COS (default) and
cosφ (read)>cosφ (set min)
or
– DRY LOGIC=CURR and
CURR (read current)>CURR MIN (set min current)
it means that the pump is operating with water in the system, so the control
panel lets it run, otherwise it is stopped due to dry running.
If the pressure drops to P (read)<(P2-ΔP2) again, the other pump starts
running (if there are two) and the control panel then checks the cosφ of the
second pump, using the same logic as for the first one.
When the pressure rises to P (read)>P2 again, the second pump is switched off, leaving the first one running (if there are
two). If the pressure rises to P (read)>P1, the pump that was left running is also switched off.
48 | ENGLISH
4-20
mA
Ratiometric
pressure
transducer
0-10 V
Factory configuration
Parameter
Value
to be configured
3.5 bar
P1
0.5 bar
ΔP1
2.5 bar
P2
0.5 bar
ΔP2
COSFI
ON
REC TIME
2 min
MAX REC T
60 min
Pressure transducer
P (bar)
PRESSURE
P1
P2
ON
ON
OFF
ON
OFF
OFF
P (bar)
PRESSURE
P1
ON
OFF
P1-∆P1
P2-∆P2
t (sec)
OFF
ON
ON
ON
P1-∆P1
t (sec)
ON

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E1 triE2 monoE2 tri

Table of Contents