Word 2 (Ind); Word 3 (Pwe1); Word 4 (Pwe2) - Mitsubishi Electric FR-A5NP Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-A5NP:
Table of Contents

Advertisement

5.2 Word 2 (IND)

Bits
Id
0-7
pp
8-15
IND

5.3 Word 3 (PWE1)

Bits
Id
0-15
PWE1

5.4 Word 4 (PWE2)

Bits
Id
0-15
PWE2
INVERTER PROFIBUS DATA WORD DEFINITION
Page Index.
Some special parameters require a page Index. If it is not
needed it should be set to 0.
If IND = 01, for system environment variables, the following
cases specify different blocks of SEV's:
0 = sev_I, block I
1 = sev_II, block II, alarm history
2 = sev_III, block III
Parameter Index.
Specifies the area from which the Specific Parameter
Number (PNU) is being accessed (see page 21):
0h = real-time monitor area
1h = system environment variable area (3 blocks)
2h = normal parameter area
3h = 900f parameter area
4h = 900% parameter area
6h = Time/Prog Settings (frequency component)
7h = Time/Prog Settings (direction component)
8h = Time/Prog Settings (time component)
Reserved and should be set to 0
Parameter Value.
The actual data transferred in a telegram.
If a task could not be executed (AK response Id = 7), the
PWE indicates the type of error detected:
0h = no error
1h = unsupported task (including busy writing state)
2h = invalid Index (IND)
3h = invalid Parameter Number (PNU)
4h = dual-port read failure
5h = dual-port write failure
6h = invalid page
41h = mode error
42h = instruction code error
43h = data range error
19
Definition
Definition
Definition