6.2
Notes on Rectification of Faults
Operating faults are often attributable to simple causes which can easily be rectified. The following
table provides remedies for these.
Symptom
7-segment displays
and LED's are not illu-
minated
7-segment display not
illuminated at one com-
ponent
F and 6 blinking
(receiver)
F and 7 blinking
(receiver)
F and 8 blinking
(receiver)
F and 9 blinking
(receiver)
8. permanently illumi-
nated
F glows continuously,
interrupted by the fault
number
The decimal point of
the transmitter´s 7-
segment display glows
(testinput active)
7
Cleaning
The cover disks in the transmitter and receiver must be cleaned regularly, depending on the amount
of dirt. Illumination of the „weak reception signal" message in the display of the receiver indicates
when cleaning is necessary at the latest.
For the cleaning of the Plexiglass cover disks, we recommend a mild detergent. The plexiglass
cover disks are highly resistant to dilute acids and alkalis, and against organic solvents to a limited
extent.
Leuze
lumiflex
Measures for fault rectification
Check the 24 V DC power supply
Check the supply voltage,
Check the connecting cable,
Replace the unit if necessary
External short circuit at OSSD1 to 0 V, or
cross circuit, or connecting cable respectively
device interchanged
External short circuit at OSSD1 to +24 V,
or cross circuit
External short circuit at OSSD2 to 0 V,
or cross circuit
External short circuit at OSSD2 to +24 V,
or cross circuit
Hardware fault, replace unit
Fault determined in the unit, replace unit (detailed
fault code is outputted via the serial interface)
Jumper 3-4 in the transmitter end cap is missing or
endcap of transmitter and receiver have been ex-
changed