Step 11 Optional: Extending the power
cable
1
Prepare the following tools.
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
0.79xØ0.26
(inch(mm))
(20xØ6.5) (HxOD)
Width 0.75 inch
Insulation tape
(19 mm)
Contraction tube
2.76xØ0.31
(inch(mm))
(70xØ8.0) (LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
•
Peel off 0.79 inch (20 mm) of cable shields from the
pre-installed tube.
CAUTION
•
For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
•
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
•
If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance (reduction of passing current)
and consequently may result in a fire.
Power cable
0.79 (20)
7.09 (180)
7.09 (180)
4.72 (120)
2.36 (60)
0.79 (20)
0.79 (20)
0.79 (20)
Shape
Unit : inch(mm)
0.79 (20)
0.79 (20)
2.36 (60)
4.72 (120)
Pre-installed
tube for the
power cable
3
Insert both sides of core wire of the power cable into the
connection sleeve.
•
Method 1: Push the core wire into the sleeve from
both sides.
•
Method 2: Twist the wire cores together and push it
into the sleeve.
Method 1
Connection sleeve
4
Using a crimping tool, compress the two points and flip
it over and compress another two points in the same
location.
•
The compression dimension should be 8.0.
•
After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
Compress it 4 times
0.20 inch (5 mm)
5
Apply heat to the contraction tube to contract it.
Method 1
Contraction tube
Method 2
Connection sleeve
Compression
dimension
Method 2
Compress it 4 times
0.20 inch (5 mm)
Method 2
Contraction tube
English